Laserfiche WebLink
Integrity Tank Testing Systems, Inc. , <br /> ITTS <br /> i <br /> TEST DATA AND <br /> TEST RESULTS <br /> August 11 , 1987 <br /> Mr." Den Ueda <br /> DeW' s Auto Repair <br /> 308S. E1 Dorado , Building A <br /> Stockton, California 95203 <br /> Dear Mr. Ueda: <br /> Following is a summary of the precision testing we recently <br /> conducted on your underground storage tank(s) . <br /> Attached are copies of the test worksheets and graphs gene- <br /> rated for your submittal to the appropriate governmental agency. <br /> A tank svetem, is considered tight, according to the current <br /> rules , if the gain is less than- .02 or the loss is less than . 05 <br /> ga.tlons per one hour of testing. If the results are .beyond these <br /> parameters , you should consider taking some remedial action. <br /> TANK #/ TANK PRODUCT TEST WITHIN TICIIT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARAMETERS <br /> East 8,000 U/L Gasoline -. 02973 Yes <br /> Center 7 , 000 Reg. Gasoline +.00659/+. 01837 Yes <br /> West 5 ,000 Super Unlead. .-. 26725 No <br /> 500 Waste Oil +. 01133 Yes <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> Frank Keser <br /> Certified Tester <br /> i <br /> 800 262 ;TEST 166 Frank West Circle Stockton, CA 95206 (209) 466-8036 <br />