TABLE 6 <br /> Inspection and Testing Program <br /> CITY OF MANTECA CORPORATION YARD <br /> 120 and 210 East Wetmore Street, Manteca, California <br /> Facility Component Action Frequency/Circumstances <br /> Aboveground container Test container integrity. Combine Following a regular schedule <br /> visual inspection with another (monthly, annual, and during <br /> testing technique scheduled inspections) and <br /> whenever material repairs are <br /> made, as deemed necessary by <br /> Facility management. <br /> Container supports and Inspect container's supports and Following a regular schedule <br /> foundation foundations. (monthly, annual, and during <br /> scheduled inspections) and <br /> whenever material repairs are <br /> made. <br /> Liquid level sensing devices Test for proper operation. Monthly <br /> (overfill) <br /> II aboveground valves, piping, Assess general condition of items, Monthly <br /> and appurtenances such as flange joints, expansion <br /> joints, valve glands and bodies, <br /> catch pans, pipeline supports, <br /> locking of valves, and metal <br /> surfaces. <br />