5.5 Strainer71 L.Access strainer Yes No` N/ <br /> basket and check cap <br /> and gasket seal as <br /> well as bolts. <br /> 5.6 Filter a. Check that the finer Yes No` NT <br /> is in good condition <br /> and is within the <br /> manufacturers <br /> expected service life. <br /> Ra lace,if necessary. <br /> b. Check for leaks and / No` N/A ' <br /> decreased fuel flow <br /> -5'Flame Follow manufacturer's Yes` No I <br /> arrestors Instructions. Check for <br /> comosion and <br /> blockage of air <br /> pace es. <br /> 5.8 Leak detector Test according to No, NIA <br /> for manufacturers <br /> submersible instructions and <br /> pump authority having <br /> systems jurisdiction(AHJ). <br /> Verify leak detectors <br /> are surfed and <br /> properlyInstalled 4or <br /> above round use. <br /> 5.9 Liquid level a. Has equipment Yes Nd NIA <br /> equipment been beside to ensure proper opomr,h? <br /> b. Does equipment e No` N/A <br /> operate as required? <br /> c.Fallow <br /> manufacurer's <br /> isormucrons <br /> 5.10 Overfill a. Follow No` NIA <br /> equipment manufacturers <br /> Instructions and <br /> regulatory <br /> requirements for <br /> inspection and <br /> functionality <br /> verifleation. <br /> b. confirm device is a No' NIA <br /> surfed for above <br /> ground use by the <br /> manufacturer <br /> 6.0 Insulated Tanks <br /> AST INSPECTION STANDARD 12 SEPTEMBER 2011 <br /> COPYRIGHT©2011 Sleel Tank Institute <br />