Laserfiche WebLink
CERTIFICATE OF STAGE II VAPOR RECOVERY TESTING <br /> Z-1.4 P,Tanlvwo%gy <br /> 8900 SHOAL CREEK, BUILDING 200 <br /> AUSTIN,TEXAS 78757 <br /> (512)451-6334 <br /> FAX(512)459-1459 <br /> TEST DATE:06/11/02 WORK ORDER NUMBER2 2 2 2 5 3 1 <br /> CLIENT: 7-ELEVEN, INC. SITE: 7-ELEVEN # 19976 MKT 2237 <br /> 10220 S.W. GREENBURG ROAD 1399 N. MAIN ST. <br /> SUITE 470 @ NORTHGATE <br /> PORTLAND, OR 97223 MANTECA, CA 95336 <br /> ATTN: BOB DENINNO CONTACT: MANAGER <br /> DYNAMIC BACK PRESSURE VAPOR BLOCKAGE TEST <br /> PRODUCT DISPENSER (DRY PRESSURE) (WET PRESSURE) <br /> inches of water at flow rates: inches of water at flow rates: <br /> 20 40 1 60 80 1 100 1 Pass/ 20 40 60 80 100 Pass/ <br /> cfh cfh cfh cfh cfh fail cfh cfh cfh cfh cfh fail <br /> PRESSURE DECAY TEST <br /> AllowablE Ullage <br /> TANK# Init Press 1 min 2 min 3 min 4 min 5 min decay space Result COMMENTS <br /> PUL 3 2.00 2.00 1.99 1.98 1.98 1.98 1.96 23131 PASS 12 NOZZELS. FILL CAPS ON. WILL NOT <br /> PASS WITH FILL CAPS OFF. <br /> Tanknology appreciates the opportunity to serve you,and looks foward to working with you in the future.Please call any time,day or night, <br /> when you need us. <br /> Tanknology representative: Test conducted by: <br /> MARK SHAW ANEIL CHAND <br /> )ItA, <br /> Reviewed: Technician Certification Number:1262 <br />