Laserfiche WebLink
TANKNOLOGY <br /> Stage Il Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN It 19976 MKT 2237 1399 N.MAIN ST. MANTECA,CA.95336 <br /> Work Order#: 2222531 Date: 06/11/2002 Technician: ANEIL CHAND <br /> Product Flow Rate Calculation Air Volume Metered(ft^3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volumc Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft-3) A/L Average Pass/Fail <br /> 7.500 48.07 9.4 86.51 87.62 1.110 1.11 <br /> 4 SUPER 1.11 Pass <br /> 7.500 48.41 9.3 87.62 88.74 1.120 1.12 <br /> 4 PLUS 1.12 Pass <br /> 7.500 51.45 8.7 89.19 90.25 1.060 1.06 <br /> 4 REG 1.06 Pass <br /> 7.500 54.98 8.2 90.26 91.26 1.000 1.00 <br /> 2 SUPER 1.00 Pass <br /> 7.500 45.59 9.9 91.22 92.42 1.200 1.20 <br /> 2 PLUS 1.20 Pass <br /> Type of System Tested: Gilbarco Vapory <br />