TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN It 19976 MKT 2237 1399 N.MAIN ST. MANTECA,CA.95336 <br /> Work Order#: 2222531 Date: 06/11/2002 Technician: ANEIL CHAND <br /> Product Flow Rate Calculation Air Volume Metered(ft^3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volumc Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft-3) A/L Average Pass/Fail <br /> 7.500 51.03 8.8 98.15 99.32 1.170 1.17 <br /> 3 PLUS 1.17 Pass <br /> 7.500 47.68 9.4 99.32 100.44 1.120 1.12 <br /> 3 REG 1.12 Pass <br /> Type of System Tested: Gilbarco Vapory <br />