Laserfiche WebLink
Form 1 <br /> Source Test Tesults <br /> Static Leak Test <br /> Date: 06/11/2002 Time: 10:30 Application No. <br /> GDF Name and address: 19976 1399 N.MAIN ST. <br /> Stage II system(check one): Vapor Balance [ ] Single Hose M.P.D. [ ] <br /> Vacuum Assist [X ] Type: VAPOR VAC <br /> Stage I type(check one): Two point [X ] Manifolded? Yes [X ] <br /> Coaxial [ ] No [ ] <br /> Tank# 1 2 3 <br /> Product grade RUL MUL PUL <br /> Actual tank capacity(gallons) 9995 9995 9995 29985 <br /> Gasoline volume (gallons) 2232 2437 2085 6754 <br /> Ullage(gallons) 7663 7558 7910 23131 <br /> Initial pressure of UST, inches H2O 0 <br /> Number of nozzles served by tank 4 4 4 12 <br /> Test location: (A) Stage I vapor <br /> coupler of(B) Stage II riser B B B B <br /> Initial Pressure, inches H2O (2.0) 2.00 <br /> Pressure after 1 min. (inches H2O) 2.00 <br /> Pressure after 2 min. (inches H2O) 1.99 <br /> Pressure after 3 min. (inches H2O) 1.98 <br /> Pressure after 4 min. (inches H2O) 1.98 <br /> Final Pressure after 5 min. (inches <br /> H2O) 1.98 <br /> Allowable Final Pressure: Table IA, <br /> Table 113, Equations 9.1, 9.2 1.96 <br /> Test Status [Pass or Fail] Pass <br /> Tests Conducted By: ACHAND <br /> Test Company: TANKNOLOGY Date of Tests: 06/11/2002 <br /> Tests Witnessed By: <br />