Laserfiche WebLink
tv <br />S A N .J O A Q U I N E Environmental Health Department <br />COUNTY ' �g <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />Date: <br />WATERLOO FOODMART <br />4315 E WATERLOO RD, STOCKTON <br />April 10, 2018 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # <br />Remarks <br />304 <br />HSC 25290.1(d) Monitoring system not maintained to detect entry into secondary containment (after Jul 2004). <br />The S4 Vents 91 STP sensor failed when tested (could not get high liquid alarm), and the L18 Vent annular senor <br />failed when tested (could not go out of alarm). During the inspection, the service technician stated the vent <br />electrical penetration was leaking brine, and no brine was observed in the reservoir, and brine was observed on the <br />floor of the vent sump. In UDC 3/4, inadequate brine levels was found in the brine reservoir. The continuous <br />monitoring system shall be maintained to detect the entry of the liquid or vapor phase of the hazardous substance <br />stored in the primary containment into the secondary containment and to detect water intrusion into the secondary <br />containment. Correct immediately by having a properly licensed, trained, and certified contractor replace the failed <br />component with a functional component (LG 113-x listed, if applicable) and obtain a permit within one business day <br />from the EHD. If the failed component can't be replaced immediately, there is a possibility that the UST system may <br />be red tagged to prevent fuel inputs. <br />This is a repeat violation, Class II. <br />305 <br />HSC 25290.1(e) VPH monitoring of the interstitial spaces of the UST system is not maintained. <br />Designated operator inspection reports from May 2017 through April 2018 indicate alarms and leaks from the <br />interstitial spaces of each UDC and sumps. According to those reports, brine has been added on 6/28/17, 7/24/17, <br />8/25/17, 10/9/17, 11/16/17, 3/5/18, and 4/3/18. According to the work orders by Elite IV, brine was added on <br />1/25/18, and on that work order, it states "sensor positions are leaking too much to clear." On the work order dated <br />2/13/18, Elite IV stated "L18 Vent transition has a well known leak, and is pointless to keep refilling brine reservoir. <br />Suggest site not waste brine." On the work order dated 6/20/17 by Elite IV, and L18 alarm was present, and <br />according to the work order, "saw brine exiting from penetration boot." On the work order dated 7/12/17 by Elite IV, <br />indicates vent sump, and UDC 1/2 both have low brine levels, and "1/2 UDC level would not stabilize, and Vent <br />transition is leaking inside containment box." On the work order dated 6/13/17 by Elite IV, dispenser 1/2 brine levels <br />were low, and they attempted to add 2 cups of brine. On the work order dated 5/31/17 by Elite IV indicates L18 <br />alarm vent sump due to low brine. <br />The S4 Vents 91 STP sensor failed to indicate a high liquid alarm when tested. The interstitial space of the UST <br />shall be maintained, as designed, under constant vacuum such that a breach in the primary or secondary <br />containment is detected before the hazardous substance is released into the environment. Correct immediately by <br />having a properly licensed, trained, and certified contractor replace the failed component with a functional <br />component (LG 113-x listed, if applicable) and obtain a permit within one business day from the EHD. If the failed <br />component can't be replaced immediately, there is a possibility that the UST system may be red tagged to prevent <br />fuel inputs. <br />The L18 Vent annular sensor failed to indicate a low liquid alarm when tested. The sensors monitoring the liquid <br />level in the interstitial space shall be maintained so that a breach in the primary or secondary containment is <br />detected before the hazardous substance is released into the environment. Correct immediately by having a <br />properly licensed, trained, and certified contractor replace the failed component with a functional component (LG <br />113-x listed, if applicable) and obtain a permit within one business day from the EHD. If the failed component can't <br />be replaced immediately, there is a possibility that the UST system may be red tagged to prevent fuel inputs. <br />This is a repeat violation, Class II. <br />FA0003831 PR0231760 SC001 04/10/2018 <br />EHD 23-01 Rev. 10/31/2017 Page 6 of 8 Underground Storage Tank Program OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />