Laserfiche WebLink
Ems_ <br /> ENVIRONMENTAL��AGRICULTURAL <br /> Analytical Chemists <br /> • September 14,2017 Lab ID : STK1751096 <br /> Live Oak Geo Environmental Customer : 3-16608 <br /> Quality Control - Organic <br /> Constituent Method Date/ID Type Units Cone. QC Data DQO Note <br /> organic <br /> 1,3-Dibmmopropane 504 09/06/17:210654SBL Blank ug/L 0.5883 102% 70-130 <br /> LCS ug/L 0.5813 99.9% 70-130 <br /> LCS ug/L 0.5961 91.8% 70-130 <br /> BS ug/L 0.5821 94.5% 70-130 <br /> BSD ug/L 0.5996 92.4% 70-130 <br /> BSRPD ug/L 0.5996 0.7% 430 <br /> MDL ug/L 0.5753 93.1 % 70-130 <br /> BCP 504 09/06/17:210654SBL Blank ug/L ND <0.01 <br /> LCS ug/L 0.2477 100% 70-130 <br /> LES ug/L 0.2540 96.8% 70-130 <br /> BS ug/L 0.2480 93.7% 70-130 <br /> BSD ug/L 0.2555 98.1 % 70-130 <br /> BSRPD ug/L 0.5996 7.6% S30 <br /> QMDL ug/L 0.01946 136% 60-140 <br /> 13DBP 504.1 09/07/17:213343SBL CCV ug/L 9.975 107% 70-130 <br /> CCV u /L 7AM 113% 70-130 <br /> BCP 504.1 09/07/17:213343SBL CCVuglL 5.000 115% 70-130 <br /> CCV u /L 2.000 103% 70-130 <br /> Definition <br /> CCV :Continuing Calibration Verification-Analyzed to verify the instrument calibration is within criteria. <br /> Blank :Method Blank-Prepared to verify that the preparation process is not contributing contamination to the samples. <br /> • LCS :Laboratory Control Standard/Sample-Prepared to verify that the preparation process is not affecting analyte recovery. <br /> BS :Blank Spikes-A blank is spiked with a known amount of analyte.It is prepared to verify that the preparation process is not <br /> affecting analyte recovery. <br /> BSD :Blank Spike Duplicate of BSBSD pair-A blank duplicate is spiked with a known amount of analyte.It is prepared to verify that <br /> the preparation process is not affecting analyte recovery. <br /> BSRPD :BS/BSD Relative Percent Difference(RPD)-The BS relative percent difference is an indication of precision for the preparation <br /> and analysis. <br /> ND :Non-detect-Result was below the DQO listed for the analyte. <br /> DQO :Data Quality Objective-This is the criteria against which theAuality control data is compared. <br /> • <br /> Page 6 of 7 <br /> Corporate Offices&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory Office&Laboratory <br /> 853 Corporation Street 2500 Stagecoach Road 563 E.Undo Avenue 3442 Empresa Drive,Suite D 9415 W Goshen Avenue <br /> Santa Paula,CA 93060 Stockton,CA 95215 Chico,CA 95926 San Luis Obispo,CA 93401 Visalia,CA 93291 <br /> TEL:(805)392-2000 TEL:(209)942-0182 TEL:(530)343-5818 TEL:(805)783-2940 TEL:(559)734-9473 <br /> Env FAX:(805)525-4172/Ag FAX:(805)392-2063 FAX:(209)942-0423 FAX:(530)343-3807 FAX:(805)783-2912 FAX:(559)734-8435 <br /> CA ELAP Certification No.1573 CA ELAP Certification No.1563 CA ELAP Certification No.2670 CA ELAP Certification No.2775 CA ELAP Certification No.2810 <br />