ii <br /> equipment, (b) foundation loads and tolerable settlements, and (c) the degree of <br /> risk that can be accepted relative to unacceptable foundation performance. <br /> Because extensive glass deposits are present at the location of the boiler <br /> and turbine, we recommend that this settlement-sensitive equipment be founded on <br /> piles driven into the sands that are present below about E1 -20 to -25 ft. An <br /> allowable axial compressive capacity of about 60 to 80 kips is appropriate for <br /> 12-in.-square concrete piles. <br /> Beneath other equipment, tanks, and moderately loaded structures, we suggest <br /> that the subsurface soils be improved using dynamic deep compaction (DDC) or <br /> partial removal and replacement of the existing soils and glass. With either <br /> method, the bearing capacity of the soils is expected to be adequate for the <br /> planned equipment and structures and the potential for large and variable settle- <br /> ments will be reduced. DDC will accomplish these purposes by compacting the <br /> soils in-place whereas removal and replacement with compacted structural fill <br /> will provide a mat of engineered material that will help to spread and distribute <br /> the loads. <br /> The existing surface silty sand fill materials, when free of debris, organ- <br /> ics, and other deleterious material, are suitable for use as compacted fill. <br /> Tests also suggest that silty sand with up to 20 percent glass fragments, that <br /> are less than 3-in. in maximum dimension, is acceptable for use as fill. The <br /> approximate range of shrinkage factors for dry to slightly moist surficial soils <br /> is 5 to 12 percent. The shrinkage factor where glass-filled trenches are <br /> replaced by compacted fill is estimated to be 10 to 20 percent. <br /> The project site is located in a seismically active region of central <br /> California. The plant facility should be designed in accordance with criteria <br /> for UBC Zone 3. No evidence was found to suggest that the proposed project site <br /> will experience ground rupture due to fault movements. Provided the site is <br /> improved as recommended previously, the potential for liquefaction at this site <br /> is judged to be limited. <br /> 1144A/H-2 McClelland <br />