Laserfiche WebLink
AMERICAN NATIONAL STANDARD K61.1-1981 <br /> CUSTOMARY UNITS AND SI UNITS <br /> Minimum Distances(in feet or meters)from Container to: <br /> Nominal Capacity.of - .Line of Adjoining Property Place of <br /> Container which may be built upon, Public Institution <br /> (Gallons or Cubic Meters) Highways&Mainline of Railroad Assembly Occupancy <br /> Over 500 to 2,000 gals. 25 ft. 150 ft. 250 ft. <br /> Over 2,000 to 30,000 gals. 50 ft. 300 ft. 500 ft. <br /> Over 30,000 to 100,000 gals. 50 ft. 450 ft. 750 ft. <br /> Over 100,000 gals. 50 ft. 600 ft. 1,000 ft. <br /> Over 1.89 to 7.57 m3 7.6 in 45.7 in 76.2 in <br /> Over 7.57 to 113.56 m' 15.2 in 91.4 m 152.4 m <br /> Over 113.56 to 378.5M3 15.2 in 137.2 in 228.6 in <br /> Over 378.5 m3 15.2 m 182.9 in 304.8 in <br /> 2.5.5 Storage areas shall be kept free of readily be located inside of the container or at a point <br /> ignitable materials such as waste, weeds and outside as close as practicable to where the line <br /> long dry grass. enters the container. In the latter case, installa- <br /> tion shall be made in such manner that any undue <br /> 2.6 Container Appurtenances stress beyond the excess flow or back pressure <br /> check valve will not cause breakage between the <br /> 2.6.1 All appurtenances shall be designed for container and the valve. <br /> not less than the maximum working pressure of <br /> that portion of the system on which they are 2.6.7 Excess flow valves shall be designed <br /> installed. All appurtenances shall be fabricated with a by-pass, not to exceed a No. 60 drill size <br /> from materials proved suitable for anhydrous opening to alio v equalization of pressures. <br /> ammonia service. 2.6.8 Shut-off valves provided with an excess <br /> 2.6.2 All connections to containers except for flow valve shall be designed for proper installa- <br /> those safety relief devices, gaging devices, or tion in a container connection so that the excess <br /> those fitted with a No.54 drill sizeorifice or those flow valve will close should the shut-off valve <br /> plugged shall have shut-off valves located as close break. <br /> to the container as practicable. 2.6.9 All excess flow valves shall be plainly <br /> 2.6.3 Excess flow valves where required by and permanently marked with the name or <br /> these standards shall close automatically at the. trade-mark of the manufacturer, the catalog <br /> rated flows of vapor or liquid as specified by the number, and the rated capacity. <br /> manufacturer. The connections and line includ- 2,6.10 The filling connection shall consist of a <br /> ing valves and fittings being protected by an positive shut-off valve in conjunction with either <br /> excess flow valve shall have a greater capacity an interpal back pressure check valve or an <br /> than the rated flow of the excess flow valve. internal excess flow valve. <br /> 2.6.4 Liquid level gaging devices that require 2,6.11 Unless equipped with approved safety <br /> bleeding of the product to the atmosphere and catch, quick opening(%turn)valves shall not be <br /> which are so constructed that outward flow will used on the end of a filler hose line. <br /> not exceed that passed by a No. 54 drill size <br /> opening need not be equipped with excess flow 2.7 Piping,Tubing and Fittings <br /> valves. <br /> 2.6.5 Openings from container or through 2.7.1 All piping, tubing and fittings shall be <br /> fittings attached directly on container to which made of material suitable for anhydrous ammonia <br /> pressure gage connections are made need not be service. <br /> equipped with excess flow valves if such openings 2,7,2 All piping, tubing and fittings shall be <br /> are not larger than No. 54 drill size. designed for a pressure not less than the <br /> 2.6.6 Excess flow and back pressure check maximum pressure to which they may be sub- <br /> valves where required by these standards shall jected in service. <br /> 11 <br />