Laserfiche WebLink
} i <br /> Building inspection-Division: ' t <br /> i <br /> 1. An allowable area analysis will be required to determine the need for any separation <br /> walls or fire sprinklers based,on allowable.area of the existing structures and the change <br /> in occupancy_ i <br /> 2. The 1344 soft S-1 storage building constructed under permit' BP-1101803 will need a <br /> building_permit to change the occupancy. Plans.will be required to show any additional <br /> exits and exit lighting requirements. The new use of this area will most likely'be A-2 The i <br /> plans must be prepared by an engineer or architect and shall include any modification <br /> due to the occupant load as calculated by Table 1004.1 2of the CBC <br /> 3. The 1380 sq ft S-1 canopy constructed under permit BP-1101803 will need the use ' <br /> specified and evaluated to determine if this structure will need a change in occupancy or <br /> pother modifications based on the occupancy change in the adjacent building This <br /> x, analysis may be'fncluded in the plans prepared to satisfy Item (b) <br /> 4. n Searching our records we:could- not find a permit issued for the 800 sq ft overhang <br /> attached to the 2048 sq ft barrel storage building__ A.buiidin_g permit for this structure will <br /> be .required. Please provide a description of the use of this area Modifications to the <br /> existing structure may be required to meet the code requirements for the proposed use. <br /> Alternatively, if you believe a permit has been issued,for-this structure please provide any <br />' pertinent information. <br /> Searching`our"records we-`could not find a ermit `issued far'the 800 s ft overhang <br /> i attached to the 1280 sq ft case goads storage building_ A building permit for this <br /> structure will be required. Please provide a _description of`the_.',use of this area. <br /> Modifications to the existing structure may be required to meet the code requirements for <br /> -the proposed use." .Based on the'.pr000sed use building-code related revisions may be <br /> .3 necessary to.accommodate'the change in occupancy discussed'in".Item:(b), If you <br /> believe a permit has been issued for this structure, please,provide any :pertinent <br /> information. <br /> 6 Parking spaces_will be required to accommodate pe sons with disability in compliance <br /> with Chapter`11B of the California Building Code. .. These parkinci space(s) shall be <br /> located as close as possible to.the-primary entrance to.the building <br /> 7. Based on the final occupantload of-the buildings restroom facilities must be provided in <br /> accordance with Table 422.1 based on.the occupant load factor in Table A of the <br /> California Plurribihg Code: `. .. <br /> q. FIRE CODE REQUIREMENTS: The following California Fire Code.(CFC).requirements will be j <br /> applicable to the_proposed project. 'The following conditions shall be addressed prior to <br /> submittal of a building Permit application,to the Building Inspection Division. <br /> T e CFC Section 503 Fir&.Apparatds Access Roads: <br /> 1. Durin 'events`post the westem most access road with Proved signs-placed at the <br /> entrance and along the length of the access road "NO PARKING-FIRE LANE" <br /> 2. Maintain all vertical clearances of.all driveways and access roads. <br /> 2: _,CFC., Section 906 Portable Fire_Extinguishees Provide portable fire extinguishers, with a <br /> minium ratin of 2A A0 B:C as follows: <br /> PA-1100092 (SA, RA) Conditions of Approval 5 i <br />