Laserfiche WebLink
NW, ,.d <br /> 15. Using a hose, fill the coalescer with fresh water and allow water to flow until the coalescer <br /> overflows into the treatment tank. Stop the flow of water to the coalescer. <br /> 16. Ensure that all three system switches on the control panel (circulating pump, sump pump, <br /> and fresh water makeup) are in the OFF position <br /> 17. Connect the power source to the equipment. Secure any spare power cord so that the <br /> cord cannot become immersed in water, or will chafe on any equipment, or is a hazard to <br /> operators. <br /> 18. Connect the fresh water makeup supply using a garden hose. Tum on the water supply, <br /> and ensure that no leaks occur. <br /> 19. Tum on the fresh water makeup switch on the control panel. Water should start to flow <br /> into the treatment tank. Observe that when the fresh water makeup level switch is in the <br /> OFF position, that the water turns off. Also check that when the control panel switch is <br /> placed in the OFF position, that the flow of water stops. <br /> The system is now ready for testing. <br /> 11 <br />