Laserfiche WebLink
® WorleyParsons <br /> resources&energy <br /> A tank level monitor will be <br /> Fire Water Supply/Distribution provided at ground level. <br /> Tank NFPA 22 An approved flow meter and <br /> piping to the firewater tank will <br /> be provided to test each fire <br /> Fire Pumps/Controllers NFPA 20 pump. <br /> Emergency fire department <br /> water supply connections <br /> Underground piping/loop NFPA 24 should be provided by installing <br /> a suction connection at the tank, <br /> and a fire hose pumper <br /> connection downstream of the <br /> fire pump discharge valves. <br /> Sectional control valves should <br /> be provided so that no more <br /> than five hydrants or individual <br /> suppression systems would be <br /> out of service in the event of a <br /> main break. <br /> Fire Hydrants NFPA 24 Hydrants will be spaced <=300 <br /> ft apart <br /> Lodi Energy Center 3.3 -7 LEC AFC <br /> 071508 Rev.A <br />