Laserfiche WebLink
Table 5.1A-5 <br /> NCPA Lodi Energy Center <br /> Calculation of Cooling Tower Emissions <br /> Typical Worst-Case Design Parameters <br /> Water Flow Rate, 10E6 Ibm/hr 29.99 <br /> Water Flow Rate, gal/min 60,000 <br /> Drift Rate, % 0.0005 <br /> Drift, Ibm water/hr 149.94 <br /> PM10 Emissions based on TDS Level <br /> TDS level, ppm (from W-P specs) 3000 <br /> PM10, Ib/hr 0.45 <br /> PM10, Ib/day 10.8 <br /> PM10, tpy 1.97 <br /> Based on 8760 hrs/yr <br />