Laserfiche WebLink
the basin floor. A two SF dent in the lower side looks poor but not sharp nor particularly threatening <br /> to AST. Paint is good and signage Indicates contents and accumulation start date. <br /> Tank 3,The UL80 AST's openings should be closed to prevent water or debris accumulation. If empty <br /> and temporarily out of service"Empty"should be noted on the tank. <br /> Tank 4, The UL80 AST's openings should be closed to prevent water or debris accumulation. If empty <br /> and temporarily out of service"Empty"should be noted on the tank. <br /> Tank 5, The poly vertical waste antifreeze AST in the shop should continue in service with ongoing <br /> record of pickup and start accumulation dates. Protection from possible forklift penetration may be a <br /> consideration. <br /> The site's exterior southwestern parking area's block wall containment needs repair, control on <br /> drainage outlet(lockable valve or pipe plug and sealed joints in floor with fuel resistant epoxy. <br /> Controlled drainage record and detention of precipitation In a contained basin, requiring active <br /> participation to drain, necessitates a lockable valve or plug on the 1 Y:IN drain. A record of witnessed <br /> deliberate drainage must remain and be available at the site. <br /> A copy of this plan, inspections (frequency determined by San Joaquin County COPA) and records of <br /> training are to be maintained at the site for a period of three(3)years. <br /> Inspector: Date: <br /> Daniel K. Barber <br /> STI certified inspector, Steel Tank Institute, Level Il,AST 8AC 18709. j <br /> MW <br /> 6 <br /> r i <br /> 'X <br /> S9 -r'i <br />