STI Aboveground Storage Tank Report Formal External Inspection COVEY AUTO EXPRESS,Stockton,CA <br /> Storage Tank Report 1/21/2014 Tank No. 1 Used Oil <br /> — Weather: Clear moderate <br /> Inspection Goal Methods Employed <br /> 7.2 DETERMINE ORIGINALResults <br /> SHELL THICKNESS Results <br /> per mfg. <br /> 7.2.1 Review original documentation. Not Available <br /> 7.2.2 Consult tank manufacturer. Elaine at Bakersfield <br /> 7.2.3 Examine tank labels for evidence of widely accepted tank Reg-# ULP794796 <br /> standard,such as Underwriters Laboratories Standard UL142. UL142 Standard <br /> 7.2.4 Measure shell thickness of several areas with no corrosion 0.2 IN,exterior <br /> 7.3 HORIZONTAL AST Requirements in addition to applicable items in 7.1: HORIZONTAL <br /> 7.3.1 Inspect shell plates, Inspect areas accessible without entering AST. Concentrate <br /> welds where corrosion is likely.If significant internal corrosion is <br /> detected,further investigation using Ultrasonic Testing Scans <br /> (LITS)is required, <br /> 7,3,2 Inspect shell Inspect for changes made after AST was fabricated.Record N/A <br /> attachments repads and/or Insert plates.Inspect welds for signs of stress <br /> and corrosion. <br /> 7.4 VERTICAL or Requirements in addition to applicable items In 7-1: N/A <br /> RECTANGULAR AST <br /> 7.4.1 Inspect shell plates, Inspect areas accessible without entering AST, Concentrate OK Ultra Sonic <br /> welds where corrosion is likely.If significant internal corrosion is measurements,visible <br /> detected,further Investigation using UTS is required. underneath&on PCC Roo, <br /> 7.4.2 Inspect shell Inspect for changes made after AST was fabricated. Record N/A <br /> attachmentsrepads and/or insert plates.Inspect welds for signs of stress <br /> and corrosion. <br /> 7.4.3 Vertical AST Roof Inspect for low areas,standing water,paint failure,holes and N/A <br /> corrosion.Take Ultrasonic Thickness Testing(UTT)readings on <br /> roof and record results. If significant internal corrosion is <br /> detected,further Investigation using UTS is required. <br /> 7.4.4 DOUBLE WALL& Requirements in addition to applicable items in 7.1: N/A <br /> DOUBLE BOTTOM AST <br /> 7.4.5 Leak Detection Verify that the leak detection equipment method is operating N/A <br /> If the tank is so equipped. <br /> 7.4.6 Inspect Interstice Check for leak or liquid in interstice,D—ot vented to NOTE Secondary Shell <br /> atmosphere. Vent should be plugged <br /> with metal not PVC <br /> 7.4.7 Double bottom Double-bottom ASTs require UTT readings of areas that are WA <br /> single-wall.Double-wall ASTs do not require UTT readings. <br /> 7.5 INSULATED AST Requirements in addition to applicable items in 7.1 to 7.4. N/A <br /> 7.5.1 Remove insulation Remove insulation in areas where mold or moisture Is present N/A <br /> Of likely to accumulate and examine metal surface for corrosion. <br /> 7.5.2 Verify damage extent If Insulation damage is suspected,remove Insulation until N/A <br /> extent and nature of corrosion has been established. <br /> 7.5.3 Take UTT readings Take LITT readings on shell and record results. If significant N/A <br /> corrosion is detected,further investigation using UTS is <br /> required. <br /> 7.5.6 FIELD ERECTED AST Additional requirements for field-erected ASTs are included in N/A <br /> SP001 Appendix B. <br /> 7.7 FINAL REPORT Include:Field data,measurements,pictures,drawings,tables Dated 1/21/14 Reinspect <br /> and an inspection summary,identify unacceptable conditions in 5years or as specified in <br /> and recommended corrective actions.Determine the SPCCP or hazardous waste <br /> suitability for continued service.Include the next scheduled regulations <br /> formal external or internal inspection as applicable.Include <br /> inspector's name and certification number in the report <br />