Laserfiche WebLink
STI Aboveground Storage Tank Report Formal External Inspection COVEY AUTO EXPRESS,Stockton, CA <br /> Storage Tank Report 1/21/2014 Tank No.2—Used Oil Weather: Clear moderate <br /> Inspection Goal Methods Employed Results <br /> 7.2 DETERMINE ORIGINAL SHELL THICKNESS <br /> 7.2.1 Review original documentation. Not Available <br /> 7.2.2 Consult tank manufacturer. <br /> 7.23 Examine tank labels for evidence of widely accepted tank N/A <br /> standard,such as Underwriters Laboratories standard UL342. <br /> 7.2.4 Measure shell thickness of several areas with no corrosion 0.105 IN,12 ga <br /> measured UTT <br /> 7,3 HORIZONTAL AST Requirements in addition to applicable items in 7.1: HORIZONTAL <br /> 7.3.1 Inspect shell plates, Inspect areas accessible without entering AST. Concentrate Sound but dented <br /> welds where corrosion is likely.If significant internal corrosion is <br /> detected,further investigation using Ultrasonic Testing Scans <br /> (UTS)is required. <br /> 7.3.2 Inspect shell Inspect for changes made after AST was fabricated.Record N/A <br /> attachments repads and/or insert plates.Inspect welds for signs of stress <br /> and corrosion. <br /> 7,4 VERTICAL or Requirements in addition to applicable items In 7.1: N/A <br /> RECTANGULAR AST <br /> 7.4.1 Inspect shell plates, Inspect areas accessible without entering AST. Concentrate OK Ultra sonic <br /> welds where corrosion is likely.If significant internal corrosion is measurements,visible <br /> detected,further investigation using UTS Is required. underneath&on PCC floor <br /> 7,4,2 Inspect shell Inspect for changes made after AST was fabricated. Record WA <br /> attachments repads and/or insert plates.Inspect welds for signs of stress <br /> and corrosion. <br /> 7.4.3 Vertical AST Roof Inspect for low areas,standing water,paint failure,holes and N/A <br /> corrosion.Take Ultrasonic Thickness Testing(UTT)readings on <br /> roof and record results. If significant internal corrosion is <br /> detected,further Investigation using UTS is required. <br /> 7,4,4 DOUBLE WALL& Requirements in addition to applicable items in 7.1: N/A <br /> DOUBLE BOTTOM AST <br /> 7.4,5 Leak Detection Verify that the leak detection equipment method is operating N/A <br /> if the tank is so equipped. <br /> 7.4.6 Inspect Interstice Check for leak or liquid in interstice,not vented to N/A <br /> atmosphere. <br /> 7.4.7 Double—bottom Double-bottom ASTs require UTT readings of areas that are N/A <br /> sin le•wall.Double-wall ASTs do not require UTT readings. <br /> 7,5 INSULATED AST Requirements in addition to applicable items In 7.1 to 7.4. N/A <br /> 7.5.1 Remove insulation Remove insulation in areas where mold or moisture is present N/A <br /> or likely to accumulate and examine metal surface for corrosion. <br /> 7.5.2 Verify damage extent If insulation damage is suspected,removeinsulation until N/A <br /> extent and nature of corrosion has been established. <br /> 7.5.3 Take tTrT readings Take LITT readings an shell and record results. If significant N/A <br /> corrosion is detected,further investigation using UTS is <br /> required. <br /> 7.5.6 FIELD ERECTED AST Additional requirements for field-erected ASTs are included in N/A <br /> SP001 Appendix B. <br /> 7,7 FINAL REPORT Include:Field data,measurements,pictures,drawings,tables Dated 1/21/14 Re-inspect <br /> and an inspection summary,identify unacceptable conditions in 5years or as specified in <br /> and recommended corrective actions.Determine the SPCCP or hazardous waste <br /> suitability forcontinued service.Include the next scheduled regulations <br /> formal external or Internal inspection as applicable.Include <br /> inspectors name and certification number in the report <br />