A. GENERAL <br />1. THE "GENERAL CONDITIONS" AND "GENERAL REQUIREMENTS" OF THE ARCHITECTURAL <br />SPECIFICATIONS GOVERN WORK UNDER ELECTRICAL. <br />2. PROVIDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES TO CONSTRUCT AND <br />INSTALL COMPLETE NEW ELECTRICAL SYSTEMS AS DESCRIBED HEREIN AND SHOWN ON <br />THE DRAWINGS. <br />3. ANY APPARATUS, APPLIANCE, MATERIAL OR WORK NOT SHOWN ON DRAWINGS BUT <br />MENTIONED IN THE SPECIFICATIONS, OR VICE VERSA, OR ACCESSORIES NECESSARY <br />TO MAKE THE WORK COMPLETE IN ALL RESPECTS AND READY FOR OPERATION, EVEN <br />IF NOT PARTICULARLY SPECIFIED, SHALL BE FURNISHED AND INSTALLED BY THE <br />CONTRACTOR WITHOUT ADDITIONAL EXPENSE TO THE OWNER. <br />4. DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, <br />ELBOWS OR OTHER SPECIFIC ELEMENTS WHICH MAY BE REQUIRED FOR PROPER <br />INSTALLATION OF WORK. SUCH WORK SHALL BE VERIFIED AT THE JOB SITE AND <br />THE REQUIRED ACCESSORIES AND ROUTING SHALL BE PROVIDED TO COMPLETE THE <br />WORK AT NO ADDITIONAL COST TO THE OWNER. THE RIGHT IS RESERVED TO MAKE <br />ANY REASONABLE CHANGES IN OUTLET, LIGHTING OR EQUIPMENT LOCATIONS, PRIOR <br />TO ROUGH -IN WITHOUT ANY ADDITIONAL COST TO THE OWNER. "REASONABLE <br />CHANGE" BE INTERPRETED AS INCLUDING ANY CHANGES OF UP TO SIX FEET FROM <br />THE LOCATIONS INDICATED ON THE DRAWINGS. <br />5. CONTRACTOR SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS AND PAY <br />ALL TAXES, FEES AND OTHER COSTS IN CONNECTION WITH THIS WORK. HE SHALL <br />OBTAIN ALL REQUIRED CERTIFICATES OF INSPECTION FOR HIS WORK AND DELIVER <br />SAME TO THE OWNER BEFORE REQUEST FOR ACCEPTANCE AND FINAL PAYMENT FOR <br />THE WORK. <br />6. WORK AND MATERIALS SHALL CONFORM TO THE LATEST RULES OF THE NATIONAL <br />BOARD OF FIRE UNDERWRITERS' CODE, REGULATIONS OF THE STATE FIRE MARSHAL, <br />AND WITH APPLICABLE LOCAL AND STATE CODES. NOTHING IN THESE <br />SPECIFICATIONS SHALL BE CONSTRUED TO PERMIT WORK NOT CONFORMING TO THE <br />MOST STRINGENT APPLICABLE CODES. <br />7. THE 2016 CBC, CEC AND CAL. ENERGY CODE PLUS THE 2016 SF ELECT. CODE AND ANY <br />LOCAL AMENDMENTS TO THE FOREGOING CODES, AND ELECTRICAL REQUIREMENTS <br />ESTABLISHED BY THE STATE AND LOCAL FIRE MARSHALS ARE HEREBY MADE PART OF <br />THESE SPECIFICATIONS. THE CONTRACTOR SHALL NOTIFY THE OWNER OF ANY PART <br />OF THE WORK HE BELIEVES TO BE IN CONFLICT WITH THESE CODES AND <br />REGULATIONS. <br />8. ELECTRICAL DRAWINGS ARE ARRANGED FOR CONVENIENCE ONLY AND DO NOT <br />NECESSARILY DETERMINE WHICH TRADE PERFORMS THE VARIOUS PORTIONS OF THE <br />WORK. THE CONTRACTOR SHALL PERFORM ALL NECESSARY WORK TO JOIN WITH OR <br />RECEIVE WORK OF OTHER TRADES. WORK SHALL BE COORDINATED WITH ALL TRADES <br />TO PROVIDE ADEQUATE CLEARANCE AND ELIMINATE CONFLICTS. <br />9. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO SUBMITTING HIS PROPOSAL <br />AND FAMILIARIZE HIMSELF WITH EXISTING SITE CONDITIONS. INFORMATION ON <br />DRAWINGS RELATIVE TO EXISTING SITE CONDITIONS IS APPROXIMATE. DURING <br />THE PROGRESS OF CONSTRUCTION, DEVIATIONS FOUND NECESSARY TO CONFORM TO <br />ACTUAL CONDITIONS SHALL BE REPORTED TO THE OWNER. CONTRACTOR IS <br />RESPONSIBLE FOR ANY DAMAGE CAUSED TO EXISTING SYSTEMS. <br />10. SHOP DRAWINGS SHALL BE SUBMITTED TO OWNER ON ALL MAJOR PIECES OF <br />ELECTRICAL EQUIPMENT, INCLUDING LIGHT FIXTURES, STARTERS, CIRCUIT <br />BREAKERS AND PANELBOARDS AND DEVICES. EACH ITEM OF THE SHOP DRAWINGS <br />SHALL BE PROPERLY LABELED, INDICATING THE INTENDED SERVICE OF THE <br />MATERIAL, THE PROJECT NAME AND THE ELECTRICAL CONTRACTOR'S NAME. WHEN <br />AN ERROR IN THE SHOP DRAWINGS IS NOT DETECTED IN THE REVIEW, THIS DOES <br />NOT GRANT THE CONTRACTOR PERMISSION TO PROCEED IN ERROR. REGARDLESS OF <br />ANY INFORMATION CONTAINED IN THE SHOP DRAWINGS, THE REQUIREMENTS OF THE <br />DRAWINGS AND SPECIFICATIONS MUST BE FOLLOWED, AND ARE NOT WAIVED OR <br />SUPERSEDED IN ANY WAY BY THE SHOP DRAWING REVIEW. <br />11. THE ELECTRICAL CONTRACTOR SHALL MAINTAIN A SET OF DRAWINGS AT THE <br />JOB SITE FOR THE EXCLUSIVE PURPOSE OF MAINTAINING A RECORD OF ALL WORK <br />INSTALLED AND TO SHOW ANY DEVIATIONS FROM THE WORK INDICATED ON THE <br />DRAWINGS. AT THE COMPLETION OF THE PROJECT, ONE SET OF REPRODUCIBLE <br />DRAWINGS, SHOWING ALL AS -BUILT CONDITIONS, SHALL BE DELIVERED TO THE <br />OWNER FOR ACCEPTANCE PRIOR TO FINAL PAYMENT. <br />12. THE RIGHT IS RESERVED TO INSPECT AND TEST ANY PORTION OF THE EQUIPMENT <br />AND/OR MATERIALS DURING THE PROGRESS OF ITS ERECTION. THE CONTRACTOR <br />SHALL TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE <br />CONNECTING ANY FIXTURES OR EQUIPMENT. A FULL-SCALE WORKING TEST WITH <br />ALL LIGHTS, EQUIPMENT, APPLIANCES, ETC., IN OPERATION SHALL BE <br />MADE, IN THE PRESENCE OF THE OWNER OR HIS REPRESENTATIVE, <br />AND THE ELECTRICAL SYSTEMS PROVEN SATISFACTORY FOR OPERATION AND FREE <br />FROM DEFECTS. ANY DEFECTS FOUND SHALL BE REMEDIED IMMEDIATELY BY THE <br />CONTRACTOR. <br />13. ON COMPLETION OF THE ENTIRE INSTALLATION, THE APPROVAL OF THE OWNER <br />SHALL BE SECURED, COVERING THE INSTALLATION THROUGHOUT. THE CONTRACTOR <br />SHALL OBTAIN AND PAY FOR A CERTIFICATE OF APPROVAL FROM THE PUBLIC <br />AUTHORITIES HAVING JURISDICTION. A FINAL INSPECTION CERTIFICATE SHALL <br />BE SUBMITTED TO THE OWNER PRIOR TO FINAL PAYMENT. ANY AND ALL COST <br />INCURRED FOR FEES SHALL BE PAID FOR BY THE CONTRACTOR. <br />14. COORDINATE ALL OUTAGES AND CUT -OVERS WITH THE OWNER. POWER SHALL NOT BE <br />INTERRUPTED TO THE OCCUPIED PORTIONS OF THE BUILDING DURING BUSINESS <br />HOURS, EXCEPT BY SPECIAL PERMISSION OF THE OWNER. <br />15. PROVIDE UNDERWRITERS' LABORATORIES, INC. OR ETL TESTING LABORATORIES, <br />INC. LISTED AND LABELED EQUIPMENT FOR ALL ITEMS FOR WHICH U.L CARRIES A <br />LISTING OR LABELING, UNLESS ITEMS ARE SPECIFICALLY EXEMPTED. <br />B. RACEWAYS AND FITTINGS <br />1. METALLIC CONDUIT INCORPORATED IN ELECTRICAL WORK SHALL COMPLY WITH ALL <br />CODES AND AMERICAN STANDARDS ASSOCIATION C80-1-1958 (NEMA -110) AND C80- <br />3-1958 (NEMA -112). <br />2. RIGID CONDUIT SHALL BE OF THREADED TYPE, HOT DIP GALVANIZED STEEL OR <br />ALUMINUM. ELECTRICAL METALLIC TUBING SHALL BE GALVANIZED STEEL AND <br />MAXIMUM SIZE SHALL BE 2 INCHES. ALL STEEL CONDUIT SHALL BE PROTECTED BY <br />AN OVERALL ZINC COATING. FLEXIBLE CONDUIT SHALL BE STEEL; MINIMUM 1/2 <br />INCH SIZE, FITTINGS SHALL BE OF SCREWED WEDGE TYPE. NEOPRENE JACKETED <br />LIQUIDTIGHT FLEXIBLE CONDUIT SHALL BE USED IN LOCATIONS EXPOSED TO <br />WEATHER OR DAMPNESS AND FOR ALL MOTOR FINAL CONNECTIONS, WITH SUITABLE <br />WATERPROOF FITTINGS. <br />3. EMT CONNECTORS AND COUPLINGS SHALL BE STEEL SET SCREW OR COMPRESSION TYPE; <br />TYPE. CONDUIT TERMINATIONS 1-1/4 INCH OR LARGER SHALL BE EQUIPPED <br />WITH APPROVED INSULATED BUSHINGS. <br />CRIMP -ON TYPE IS NOT ACCEPTABLE. CONNECTORS IN PLENUMS SHALL BE COMPRESSION <br />4. RIGID STEEL CONDUIT SHALL BE USED FOR RUNS LARGER THAN 2". <br />5. ELECTRICAL METALLIC TUBING MAY BE USED ONLY IN INTERIOR, DRY <br />APPLICATIONS NOT SUBJECT TO PHYSICAL DAMAGE. <br />6. FLEXIBLE CONDUIT SHALL BE USED FOR FINAL CONNECTIONS TO ALL VIBRATING <br />EQUIPMENT (INCLUDING TRANSFORMERS) AND RECESSED LIGHT FIXTURES. <br />CONNECTIONS TO ROTATING EQUIPMENT SHALL BE WITH LIQUIDTIGHT FLEXIBLE <br />CONDUIT WITH A MINIMUM 270 DEGREE BEND. <br />7. CONCEAL ALL CONDUIT WHEREVER POSSIBLE EXCEPT IN MECHANICAL OR ELECTRICAL <br />EQUIPMENT AREAS. EXPOSED CONDUIT SHALL BE RUN PARALLEL WITH OR AT RIGHT <br />ANGLES TO THE LINES OF THE BUILDING. CONDUIT CONCEALED IN CEILING <br />SPACES SHALL BE RUN PARALLEL TO BUILDINGS LINES WHERE POSSIBLE. <br />8. CONDUIT SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE; SUPPORTS FROM <br />AIR CONDITIONING DUCTS OR PIPING SHALL NOT BE PERMITTED. SECURE ALL <br />CONDUITS TO OUTLET BOXES, JUNCTION BOXES OR CABINETS WITH LOCKNUTS <br />OUTSIDE AND LOCKNUTS WITH BUSHINGS INSIDE. REAM CONDUITS AFTER THREADS <br />ARE CUT; ENDS SHALL BE CUT SQUARE AND SHALL BUTT SOLIDLY INTO COUPLINGS <br />AND CONNECTORS. <br />SPECIFICATIONS <br />9. CONDUITS SHALL BE CONTINUOUS FROM OUTLET TO OUTLET AND FROM OUTLETS TO <br />CABINETS, JUNCTION OR PULL BOXES, AND SHALL ENTER AND BE SECURED AT ALL <br />BOXES SO THAT EACH SYSTEM SHALL BE ELECTRICALLY CONTINUOUS THROUGHOUT. <br />10. A NYLON PULL CORD SHALL BE LEFT IN ALL CONDUITS IN WHICH PERMANENT <br />WIRING IS NOT INSTALLED. <br />11. METAL -CLAD CABLE (MC) MAY BE USED ONLY IN INTERIOR, CONCEALED DRY <br />APPLICATION WITHIN BUILDING AND FOR BRANCH CIRCUITS ONLY. <br />12. ANY ELECTRICAL RACEWAY PENETRATION THROUGH FIRE RATED WALLS SHALL <br />SHALL BE SEAL WITH APPROVED FIRE RESISTANCE SEALANT. <br />C. WIRE AND CABLE <br />1. CONDUCTORS SHALL BE COPPER AND RATED AT NOT LESS THAN 600 VOLTS, EXCEPT <br />FOR SIGNAL CABLE SPECIFICALLY RATED LOWER. FOR POWER AND LIGHTING, <br />MINIMUM SIZE SHALL BE NUMBER 12 AWG; FOR SIGNAL CABLES NUMBER AND SIZE <br />AS INDICATED. ALL WIRE NUMBER 8 AWG OR LARGER SHALL BE STRANDED. <br />2. FIXTURE EXTENSIONS SHALL BE NUMBER 12 AWG EXCEPT THOSE INDIVIDUAL <br />FIXTURE EXTENSIONS THAT DO NOT EXCEED 4 FEET IN LENGTH MAY BE NUMBER 14 <br />AWG. FIXTURE EXTENSIONS SHALL HAVE TEMPERATURE RATING TO CONFORM TO <br />INDIVIDUAL FIXTURE REQUIREMENTS. <br />3. WIRING SHALL BE TYPE THWN OR THHN, MINIMUM 75 DEGREES C. INSULATION. <br />FEEDERS SIZED NUMBER 2 AWG AND ABOVE SHALL BE TYPE THW, 75 DEGREES C. <br />INSULATION, OR THHN (90o RATED), AND SIZED PER TABLE 310.16 OF THE NEC & CEC. <br />4. SPECIAL PRE -MANUFACTURED CABLING SYSTEMS, SUCH AS MODULAR WIRING AND MC <br />TYPE CABLE MAY BE USED IN THIS FACILITY EXCEPT FOR CABLING SERVING FIRE <br />ALARM AND LIFE SAFETY SYSTEMS OR FUNCTIONS. <br />5. ALL WIRING SHALL BE COLOR CODED AS FOLLOWS: 120/208 VOLT SYSTEM PHASE <br />"A" - BLACK; PHASE "B" - RED; NEUTRAL -WHITE; GROUNDING CONDUCTOR - GREEN. <br />6. ALL WIRE AND CABLE SHALL BE INSTALLED IN RACEWAY EXCEPT AS SPECIFICALLY <br />PERMITTED OTHERWISE. VERTICAL RUNS OF CABLE SHALL BE SUPPORTED AT <br />JUNCTION AND PULL BOXES PER CODE REQUIREMENTS. <br />7. AT EACH FIXTURE OUTLET A LOOP OR END OF WIRE NOT LESS THAN 8" LONG SHALL <br />BE LEFT FOR CONNECTION TO FIXTURES. <br />8. TELEPHONE/CABLES WILL BE FURNISHED AND INSTALLED TO EACH OUTLET SHOWN ON <br />DRAWINGS BY ELECTRICAL CONTRACTOR. <br />9. TELEVISION CABLES WILL BE FURNISHED AND INSTALLED TO EACH OUTLET SHOWN ON <br />DRAWINGS BY ELECTRICAL CONTRACTOR. COORDINATE WITH CABLE TV COMPANY FOR <br />CABLE TERMINATIONS AND RECUIREMENTS. <br />D. SPLICES AND INSULATION <br />1. WIRE NUT CONNECTORS SHALL BE MANUFACTURED BY THOMAS & BETTS, 3M, IDEAL <br />OR APPROVED EQUAL. COMPRESSION TYPE WIRE CONNECTORS SHALL BE <br />MANUFACTURED BY THOMAS & BETTS, 3M OR APPROVED EQUAL. MECHANICAL <br />SCREWED COMPRESSION TYPE CONNECTORS SHALL BE MANUFACTURED BY BURNDY, <br />ILSCO OR APPROVED EQUAL. <br />2. JOINTS IN BRANCH CIRCUITS SHALL OCCUR ONLY WHERE SUCH CIRCUITS DIVIDE <br />AND SHALL CONSIST OF ONE THROUGH CIRCUIT TO WHICH SHALL BE SPLICED THE <br />BRANCH FROM THE CIRCUIT. NO SPLICES SHALL BE MADE IN CONDUCTORS EXCEPT <br />AT OUTLET BOXES, JUNCTION BOXES AND SPLICE BOXES. <br />3. ALL JOINTS FOR POWER WIRING NO. 10 AWG OR SMALLER SHALL BE MADE WITH <br />WIRE NUTS OR COMPRESSION TYPE CONNECTORS. JOINTS IN SIGNAL CABLES SHALL <br />BE MADE ONLY WITH COMPRESSION TYPE CONNECTORS. <br />4. ALL JOINTS OR SPLICES FOR NO. 8 AWG OR LARGER SHALL BE MADE WITH A <br />MECHANICAL COMPRESSION CONNECTOR. AFTER THE CONDUCTORS HAVE BEEN MADE <br />MECHANICALLY AND ELECTRICALLY SECURE, THE ENTIRE JOINT OR SPLICE SHALL <br />BE COVERED WITH TAPE TO MAKE THE INSULATION OF THE JOINT OR SPLICE EQUAL <br />TO THE INSULATION OF THE CONDUCTORS. <br />E. WIRING DEVICES AND OUTLET BOXES <br />1. WIRING DEVICES SHALL BE LEVITON, DECORA <br />SERIES OR APPROVED EQUAL. COLOR TO BE WHITE UNLESS OTHERWISE NOTED. <br />WALL RECEPTACLE OUTLETS SHALL BE NEMA 5-20R (UNLESS OTHERWISE NOTED). <br />2. OUTLET BOXES FOR CONCEALED WORK SHALL BE ONE PIECE, PRESSED STEEL, <br />KNOCKOUT TYPE WITH ZINC OR CADMIUM COATING. BOXES SHALL NOT BE SMALLER <br />THAN 4 INCHES SQUARE NOMINAL SIZE EXCEPT WHERE LARGER SIZES ARE <br />INDICATED. PROVIDE EXTENSION RINGS, PLASTER RINGS AND COVERS NECESSARY <br />FOR FLUSH FINISH. <br />3. WALL TELEPHONE OUTLETS SHALL BE PRESSED STEEL SECTIONAL SWITCH BOXES. <br />4. MOUNT DEVICES IN APPROVED OUTLET BOXES WITH MOUNTING HEIGHTS INDICATED <br />TO CENTER OF DEVICE. WHERE MORE THAN ONE WALL SWITCH IS INDICATED AT <br />ONE LOCATION, SWITCHES SHALL BE GANGED UNDER A COMMON WALL PLATE. MORE <br />THAN 6 SWITCHES AT ONE LOCATION SHALL BE GANGED IN TWO ROWS, ONE ABOVE <br />THE OTHER. <br />5. BEFORE LOCATING OUTLET BOXES, CHECK ALL ARCHITECTURAL DRAWINGS FOR TYPE <br />OF CONSTRUCTION AND TO MAKE SURE THAT THERE ARE NO CONFLICTS WITH OTHER <br />EQUIPMENT. <br />6. BAR HANGERS SHALL BE USED TO SUPPORT OUTLET BOXES IN STUD OR FURRED <br />PARTITIONS AND CEILINGS. SCREWS SHALL BE USED WITH EXPANSION SHIELDS <br />FOR FASTENING TO CONCRETE OR MASONRY. PROVIDE APPROVED KNOCKOUT SEALS <br />ON UNUSED OPEN KNOCKOUT HOLES. <br />F. PANELBOARDS LOADCENTERS AND CIRCUIT BREAKERS <br />1. PANELBOARDS LOADCENTERS SHALL BE SEQUENCE PHASED,FACTORY ASSEMBLED,WITH COPPER <br />BUS, SIZED AS INDICATED ON DRAWINGS. PANELBOARDS SHALL BE <br />CUTLER - HAMMER, SQUARE D, GE OR APPROVED EQUAL. <br />2. CABINET SHALL BE MINIMUM 20 INCHES WIDE UNLESS OTHERWISE NOTED. FRONT <br />TRIM SHALL BE DEAD FRONT WITH HINGED DOOR, FLUSHED LOCKS AND CONTAIN A <br />TYPEWRITTEN DIRECTORY BEHIND CLEAR PLASTIC IN A METAL FRAME. <br />3. PANELBOARDS OVER 22 INCHES WIDE SHALL HAVE DOOR -IN -DOOR CONSTRUCTION, <br />FOR EASY ACCESS TO WIRING, AND THREE-POINT LOCKS ON BOTH DOORS. <br />CABINETS, DOORS AND TRIMS SHALL BE FABRICATED FROM CODE GAUGE STEEL, <br />WITH DOORS AND TRIMS PRIMED FOR FIELD PAINTING TO MATCH SURROUNDING WALL <br />FINISHES. <br />4. MOLDED CASE CIRCUIT BREAKERS SHALL BE AS MANUFACTURED BY CUTLER -HAMMER, SQUARE D, <br />OR G.E. WITH FRAME, TRIP AND SHORT CIRCUIT RATING AS <br />INDICATED ON THE DRAWINGS. <br />5. CIRCUIT BREAKERS SHALL BE OF THE BOLT -ON TYPE MOUNTING. MULTI -POLE <br />BREAKERS SHALL BE SINGLE DEVICES, IN ONE ENCLOSURE, WITH ONE OPERATING <br />HANDLE AND COMMON TRIP. <br />6. MINIMUM RMS SYMMETRICAL RATING OF CIRCUIT BREAKERS SHALL MATCH EXISTING <br />7. PANELBOARDS SHALL BE MOUNTED PLUMB AND TRIM ADJUSTED TO BE VERTICAL AND <br />COVERING ALL OPENINGS. TOP OF PANELBOARD SHALL BE MAXIMUM 6'-6" ABOVE <br />FINISHED FLOOR. REMOVE ALL WIRING FROM PANEL BOARDS WHERE CIRCUITS ARE <br />DELETED OR ABANDONED. <br />8. CIRCUIT BREAKER TERMINATIONS SHALL NOT BE DOUBLE LUGGED TO TAP OFF FOR <br />ADDITIONAL CIRCUIT RUNS. ALL BRANCH CIRCUIT TAPS SHALL BE MADE OUTSIDE <br />OF PANELS IN APPROPRIATE JUNCTION BOXES. <br />G. MOTOR DISCONNECT <br />1. DISCONNECTING DEVICES SHALL BE PROVIDED FOR EACH MOTOR. SWITCHES SHALL <br />BE MOTOR -RATED, EXCEPT WHERE OTHERWISE INDICATED. <br />2. DISCONNECT SWITCHES FOR MOTORS RATED 1/2 HP OR LARGER SHALL BE UNFUSED <br />(UNLESS OTHERWISE INDICATED), THREE POLE, 208 VOLTS IN NEMA GENERAL <br />PURPOSE OR WEATHERPROOF ENCLOSURES. <br />3. SWITCHES FOR MOTORS LESS THAN 1/2 HP SHALL BE TOGGLE TYPE, QUICK MAKE <br />AND BREAK, RATED AT 120 VOLTS, WITH THE NUMBER OF POLES REQUIRED, IN <br />SURFACE MOUNT TYPE, NEMA 1 ENCLOSURES. <br />H. GROUNDING <br />1. PROVIDE ALL GROUNDING FOR ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE <br />WITH ALL APPLICABLE CODES. INCLUDE, CONDUIT SYSTEM, MOTORS, SECONDARY <br />NEUTRAL WIRE AND MISCELLANEOUS GROUNDS REQUIRED. GROUNDING LUGS, WHERE <br />PROVIDED AS STANDARD MANUFACTURER'S ITEMS ON EQUIPMENT FURNISHED MAY BE <br />USED. THE GROUNDING SYSTEM SHALL COMPLY WITH ARTICLE 250 OF THE NEC AND CEC <br />2. PROVIDE SEPARATE GREEN INSULATED EQUIPMENT GROUND CONDUCTOR IN ALL <br />FLEXIBLE ELECTRICAL RACEWAYS. EFFECTIVELY GROUND ALL <br />FIXTURES, PANELS, CONTROLS, MOTORS, DISCONNECT SWITCHES, AND NONCURRENT <br />CARRYING METALLIC ENCLOSURES. USE BONDING JUMPERS, GROUNDING BUSHINGS, <br />LUGS, BUSES, ETC., FOR THIS PURPOSE. PROVIDE GROUNDING BUSHINGS ON ALL <br />FEEDER CONDUIT ENTRANCES TO PANELS AND EQUIPMENT ENCLOSURES AND BOND <br />BUSHINGS TO ENCLOSURES WITH MINIMUM NO. 10 AWG CONDUCTOR. CONNECT THE <br />EQUIPMENT GROUND TO THE BUILDING SYSTEM GROUND. USE THE SAME SIZE <br />EQUIPMENT GROUND CONDUCTORS AS PHASE CONDUCTORS, UP THROUGH NO. 10 AWG. <br />USE N.E.C. TABLE 250-95 FOR CONDUCTOR SIZE WITH PHASE CONDUCTORS NO. 8 <br />AND LARGER, IF NOT SHOWN ON THE DRAWINGS. <br />3. RECEPTACLES: PERMANENTLY CONNECT THE GROUND TERMINAL ON EACH RECEPTACLE <br />TO THE GREEN GROUND CONDUCTOR OR GROUNDED METAL RACEWAY SYSTEM WITH A <br />GROUND WIRE. <br />4. MOTORS: CONNECT THE GROUND CONDUCTOR TO THE CONDUIT WITH AN APPROVED <br />GROUNDING BUSHING, AND TO THE METAL FRAME WITH A BOLTED SOLDERLESS LUG. <br />BOLTS, SCREWS AND WASHERS SHALL BE BRONZE OR CADMIUM PLATED STEEL. <br />5. GROUND CONDUCTORS SHALL BE 600 VOLT - NO. 12 AWG STRANDED COPPER <br />MINIMUM, WITH GREEN INSULATION; AND SHALL BE CONTINUOUS FROM TERMINAL TO <br />TERMINAL WITHOUT SPLICE. <br />I. JUNCTION AND PULL BOXES <br />1. DRAWINGS DO NOT NECESSARILY SHOW EVERY PULL BOX REQUIRED. ADDITIONAL <br />BOXES MAY BE ADDED WHEN DESIRABLE TO SAVE LABOR AND AVOID DIFFICULTIES; <br />AND WHEN CODE REQUIREMENTS LIMIT THE NUMBER OF BENDS BETWEEN BOXES. <br />ADDITIONAL BOXES SHALL BE PROVIDED WITHOUT ADDED COST TO THE OWNER. <br />BOXES SHALL BE SIZED ACCORDING TO CODE AND SHALL BE UNDERWRITERS' <br />LABORATORIES LISTED. BOXES SHALL BE ACCESSIBLE AT THE TIME OF <br />COMPLETION AND IN FINISHED AREAS SHALL BE LOCATED ONLY AFTER APPROVAL OF <br />ARCHITECT DUE TO APPEARANCE CONSIDERATIONS. <br />2. ALL JUNCTION BOXES IN CEILING SPACES SHALL BE MARKED WITH BLACK MARKING <br />PEN AS TO THE PANEL AND CIRCUITS PASSING THROUGH THE BOX. <br />J. LABELS <br />1. WHITE CORE BLACK ENGRAVED PLASTIC NAMEPLATES SHALL BE ATTACHED TO ALL <br />EQUIPMENT (PANELBOARDS, STARTERS, ETC.) INDICATING EQUIPMENT, DESIGNATION AND <br />VOLTAGES. <br />K. DEMOLITION <br />1. CONTRACTOR SHALL EXAMINE THE WORK SITE AND COMPARE IT WITH THE DRAWINGS <br />AS THE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED. INSPECT EXISTING <br />CONDITIONS TO OBTAIN A COMPLETE UNDERSTANDING OF HOW SYSTEMS ARE <br />CONFIGURED, WHERE SYSTEMS CAN BE SAVED, AND WHAT CONSEQUENCES WILL <br />OCCUR AS A RESULT OF DEMOLITION, PRIOR TO COMMENCING ANY DEMOLITION. NO <br />ALLOWANCE SHALL BE SUBSEQUENTLY MADE FOR ANY EXTRA DUE TO FAILURE OR <br />NEGLECT BY THIS SPECIFICATION TO MAKE SUCH EXAMINATION. <br />2. WORK INCLUDED: WORK COMPRISES DEMOLITION OF ELECTRICAL SYSTEMS AS <br />REQUIRED FOR NEW WORK. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, <br />APPARATUS, TOOLS, EQUIPMENT, TRANSPORTATION, TEMPORARY CONSTRUCTION AND <br />SPECIAL SERVICES AS REQUIRED TO MAKE A COMPLETE DEMOLITION OF ELECTRICAL <br />SYSTEM AS REQUIRE. <br />3. ITEMS REMOVED AS RESULT OF THE DEMOLITION WORK SHALL BE CONSIDERED AS <br />DEBRIS AND SHALL BE DISPOSED OFF PROPERTY UNLESS OTHERWISE NOTED. <br />L. ENERGY COMPLIANCE <br />1. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL COMPLETE/SIGNED CALIFORNIA <br />ENERGY COMMISSION ACCEPTANCE FORMS "CEC-NRCA" AND INSTALLATION FORMS <br />"CEC-NRCI" ASSOCIATED WITH ALL LIGHTING AND POWER DESIGN IN THESE DESIGN <br />DRAWINGS, AND SHALL INCLUDE ALL FEE ASSOCIATED WITH THE COMPLETION OF <br />THESE FORMS. <br />ABBREVIATIONS <br />LEGEND <br />ED EM❑N DM❑N WATT METER <br />FO -S] OCCUPANCY SENSOR <br />DL DAYLIGHT SENSOR <br />NB LIGHTING NETWORK BRIDGE <br />Rc LIGHTING ROOM CONTROLLER <br />GENERAL NOTE: <br />WALL MOUNTED ELECTRICAL SWITCHES AND OUTLETS <br />SHALL BE LOCATED NO MORE THAN 48INCH TO THE <br />TOP OF BOX, NOR LESS THAN 15INCH TO THE <br />BOTTOM OF BOX ABOVE FINISHED FLOOR, <br />SEE SHEET A3,2 FOR FINAL OUTLET HEIGHT. <br />DRAWING INDEX <br />E-0.1 <br />SPECIFICATIONS, ABBREVIATIONS AND LEGEND <br />II <br />TELEPHONE OUTLET AT 18" AFF <br />E-0.3 <br />AFF <br />ABOVE FINISHED FLOOR <br />TITLE 24 COMPLIANCE FORM <br />E-0.5 <br />WAA <br />TEL <br />TELEPHONE <br />i <br />DATA OUTLET AT 18" AFF <br />E-1.2 <br />C <br />CONDUIT <br />LIGHTING PLAN <br />DATA / PHONE OUTLET AT 18" AFF <br />.rx, <br />TYP <br />TYPICAL <br />Ern1►'n►eer�l►'n <br />C.O. <br />CONDUIT ONLY <br />CABLE TV OUTLET AT 18" AFF <br />an►dd LDea1'�n <br />�e'�'�- �i►►' cJe�_-s� jrn cJ� <br />U.O.N. <br />UNLESS OTHERWISE NOTED <br />SINGLE POLE SWITCH AT 48" AFF <br />C.B <br />CIRCUIT BREAKER <br />ADR: 3119 Central Parkway, <br />Dublin CA. 94568 <br />3 -WAY SWITCH AT 48" AFF <br />TEL: 510-788-6029 <br />CKT <br />CIRCUIT <br />CEL: 510-468-0613 <br />FAX: 510-788-6039 <br />DWG <br />DRAWING <br />�D <br />DIMMER SWITCH AT 48" AFF <br />(E) <br />EXISTING TO REMAIN DESIGNATION <br />SENSOR S AT C 8 CMAAFF AL ON <br />ssi <br />ELEC <br />ELECTRICAL <br />AUTION TOMATIC ) / �oQR <br />UT❑MAIC <br />o�< <br />ELR <br />END OF LINE REGISTER <br />SINGLE OUTLET, SEE DWG. A3.2 <br />C F <br />tiF <br />FOR M❑UNTING HEIGHT <br />w No 9279 <br />EM <br />EMERGENCY <br />DUPLEX OUTLET, SEE DWG. A3,2 <br />A <br />EXP.OV30/19 <br />1. G. <br />ISOLATED GROUND <br />FOR M❑UNTING HEIGHT <br />rT9TF4tCTRkCP�R�P <br />(N) <br />NOT IN CONTRACTGFI <br />GROUND FAULT INTERRUPTER <br />FOF <br />DUPLEX OUTLET, SEE DWG. A3,2 <br />N.I.C. <br />NOT IN CONTRACT <br />FOR M❑UNTING HEIGHT <br />DOUBLE DUPLEX OUTLET, SEE DWG, <br />PNL <br />PANELBOARD <br />8 <br />A3,2 FOR M❑UNTING HEIGHT <br />Revisions <br />Date <br />GFI <br />GROUND FAULT INTERRUPTER <br />&R <br />RANGE OUTLET, SEE DWG, A3,2 <br />PERMIT SET <br />09-13-2018 <br />FOR M❑UNTING HEIGHT <br />SAD <br />SEE ARCHITECTURAL DRAWINGS <br />6WP <br />OUTLET WITH WATER -PROOF COVER, <br />SEE DWG. A32 FOR M❑UNTING HEIGHT <br />TBD <br />TO BE DETERMINED <br />®/® <br />FLOOR OUTLET <br />W.P. <br />WEATHER PROOF <br />O <br />CEILING MOUNTED OUTLET <br />(R) <br />RELOCATED <br />Preliminary Set <br />X <br />ELECTRICAL PANEL <br />E.C. <br />ELECTRICAL CONTRACTOR <br />rc <br />TIMER CLOCK <br />Design Review Set <br />Plan Check Set <br />J -BOX <br />JUNCTION AND/OR HANDY BOX <br />MOTOR C❑NNECTI❑N <br />Plan Check Resubmit <br />DCO <br />DUPLEX CONVENIENCE OUTLET <br />Construction Set <br />0� <br />DISCONNECT SWITCH <br />SPO <br />SINGLE OR SPECIAL PURPOSE OUTLET <br />TTB <br />TELEPHONE TERMINAL BOARD <br />O <br />SHEETN❑TE TAG <br />MPOE <br />MINIMUM POINT OF ENTRY <br />LED EXIT LIGHT AND EM LIGHT <br />COMBO WITH BATTERY BACKUP <br />CAM <br />CAMERA <br />EMERGENCY LIGHT W/ BATTERY BACK UP <br />ED EM❑N DM❑N WATT METER <br />FO -S] OCCUPANCY SENSOR <br />DL DAYLIGHT SENSOR <br />NB LIGHTING NETWORK BRIDGE <br />Rc LIGHTING ROOM CONTROLLER <br />GENERAL NOTE: <br />WALL MOUNTED ELECTRICAL SWITCHES AND OUTLETS <br />SHALL BE LOCATED NO MORE THAN 48INCH TO THE <br />TOP OF BOX, NOR LESS THAN 15INCH TO THE <br />BOTTOM OF BOX ABOVE FINISHED FLOOR, <br />SEE SHEET A3,2 FOR FINAL OUTLET HEIGHT. <br />DRAWING INDEX <br />E-0.1 <br />SPECIFICATIONS, ABBREVIATIONS AND LEGEND <br />E-0.2 <br />TITLE 24 COMPLIANCE FORM <br />E-0.3 <br />TITLE 24 COMPLIANCE FORM <br />E-0.4 <br />TITLE 24 COMPLIANCE FORM <br />E-0.5 <br />TITLE 24 COMPLIANCE FORM <br />E-1.0 <br />GROUND FLOOR POWER PLAN <br />E-1.1 <br />ROOF POWER PLAN <br />E-1.2 <br />SINGLE -LINE AND PANEL SCHEDULES <br />E-2.0 <br />LIGHTING PLAN <br />E-2.1 <br />LIGHT SCHEDULE & DETAILS <br />1 <br />rig <br />w <br />G <br />w <br />O <br />C� <br />G <br />z <br />Q <br />z <br />w <br />0 <br />J <br />O <br />Cz <br />G <br />Q <br />z <br />LUGo <br />LO <br />so <br />ti <br />00 <br />N <br />Q <br />U <br />z <br />O <br />U <br />O <br />U) <br />Scale: AS NOTED <br />Drawn By: C&N <br />Approved By: JP <br />Job: 18033 <br />Sheet: <br />SPECIFICATION, <br />ABBREVIATION <br />AND LEGEND <br />of: E=Oml <br />