My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO 2009 - 2018
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
F
>
FREMONT
>
2185
>
2300 - Underground Storage Tank Program
>
PR0231118
>
COMPLIANCE INFO 2009 - 2018
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
7/25/2023 2:30:31 PM
Creation date
10/21/2019 2:23:15 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2009 - 2018
RECORD_ID
PR0231118
PE
2371
FACILITY_ID
FA0003284
FACILITY_NAME
FOOD MART GASOLINE*
STREET_NUMBER
2185
Direction
E
STREET_NAME
FREMONT
STREET_TYPE
ST
City
STOCKTON
Zip
95205
APN
14113045
CURRENT_STATUS
01
SITE_LOCATION
2185 E FREMONT ST
P_LOCATION
01
P_DISTRICT
001
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
482
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone:(209)468-3420 Fax:(209)468-3433 Web:www.sogov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> FOOD MART GASOLINE' 1 185 E FREMONT ST, STOCKTON September 28 2015 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS 11,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 204 CCR 2712(i) Current monitoring plan approved by the EHD not found on site. <br /> An approved copy of the monitoring plans were not available for inspection. A copy of these plans shall be accessible <br /> on site at all times. Immediately locate and retain a copy on site. <br /> This is a Class II violation. <br /> 207 CCR 2715 Designated operator did not inspect all required items and/or the inspection reports not completed. <br /> The designated operator failed to document all the alarms from the attached alarm history on the designated operator <br /> monthly inspection reports and failed to check that they were responded to appropriately. The missing alarms <br /> include: L3 (annular)6/21/15 fuel and sensor out alarms, L3 (annular) 7/21/15 fuel alarm, T1 (87) 12/4/14 probe out <br /> alarm, and T1 (87) 12/22/14 probe out alarm. The attached alarm histories do not include tank alarms (T1, T2, T3)for <br /> the following months: October and December 2014 and January, February,April, May, July,August and September <br /> 2015. The July 21, 2015 alarm was documented on the August 2015 monthly report; however, the designated operator <br /> did not check that the alarm was responded to appropriately. During the monthly inspection, the designated operator <br /> shall review the alarm history for the previous month, check that each alarm was documented and responded to <br /> appropriately, and attach a copy of the alarm history with documentation taken in response to any alarms to the <br /> monthly report. Ensure that designated operators performing monthly inspections at this facility are including all of the <br /> required information on the reports. <br /> This is a repeat violation, Class ll. <br /> 315 HSC 25290.2(c)(1) Primary containment not tight(Jul 2003-Jun2004). <br /> The diesel filter at dispenser 1,2 was observed to be leaking into the UDC and approximately one-half cup of diesel <br /> was observed in the UDC, indicating a leak in the primary piping. All primary containment for the UST system must <br /> be tight. Immediately have a properly licensed, trained, and certified contractor repair or replace the failed component. <br /> This is a Class II violation. <br /> 320 HSC 25290.1(c3), 25290.2(c3) Secondary containment not constructed to prevent water intrusion. <br /> Water was found in the diesel STP sump. Secondary containment shall be constructed to prevent any water intrusion <br /> into the system by precipitation, infiltration, or surface runoff. Immediately remove this liquid, make a hazardous <br /> waste determination per Title 22 hazardous waste regulations, and manage accordingly. Immediately contact a <br /> properly licensed, trained, and certified contractor to address the water intrusion into the diesel STP sump under <br /> permit and inspection of the EHD. <br /> This is a Class II violation. <br /> 323 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi. <br /> The 87 VMI line leak detector failed to detect a leak when tested. All line leak detectors shall be capable of detecting <br /> a 3-gallon per hour leak at 10 psi. The service technician adjusted the leak detector, retested it, and it passed. <br /> This is a repeat violation, Class li. <br /> Received Inspector: Phone: Date: <br /> (initial): STACY RIVERA, Senior REHS � (209) 468-3440 09/28/2015 <br /> Page 5 of 6 <br />
The URL can be used to link to this page
Your browser does not support the video tag.