Laserfiche WebLink
Cecchini Trucking Company Inc. <br />SPCC Plan <br />Apri 1 2020 <br />Page 33 of 63 <br />The storage tank in the maintenance shop (Table 5) is shop -fabricated and is a <br />smaller Category 1 tank (0 to 1,100 -gallons) which only requires periodic inspections <br />with no formal external inspection required. Please see Section 6.0 in the STI SP001 <br />Guide. The facility documents all inspections of these tanks using the STI SP001 <br />Inspection Checklist (Monthly & Annual) which can be found in Appendix C in this <br />Plan. The results of all inspections (monthly and annual) are kept at the facility. <br />Table 7 — Tank Configuration and AST Category — STI SP001 <br />Tank Configuration <br />Tank has <br />CRDM? <br />Tank has <br />Spill Control? <br />AST Category <br />Single wall AST in contact with ground <br />no <br />no <br />3 <br />Single wall AST in contact with ground <br />no <br />yes <br />2 <br />Elevated tank <br />yes <br />yes <br />1 <br />AST with RPB <br />yes <br />yes <br />1 <br />AST with double -bottom <br />yes <br />yes <br />1 <br />Double-wall AST with overfill prevention <br />yes <br />yes <br />1 <br />Double-wall AST without overfill prevention <br />yes <br />no <br />3 <br />Vertical tank resting on concrete conforms with definition of RPB <br />es <br />yes <br />1 <br />Vertical tank resting on concrete (conforms with definition of RPB) <br />yes <br />no <br />3 <br />Table 8 — Table of Inspection Schedules — STI SP001 <br />AST Type and Size (U.S. gallons) <br />Category 1 <br />Category 2 <br />Category 3 <br />Shop -Fabricated ASTs <br />0-1100 <br />P <br />P <br />P, E&L(10) <br />(0-4164 liters) <br />[P, E&L(5), 1(10)] <br />1101 -5,000 <br />P <br />P, E&L(10) <br />or <br />(4168-18,927 liters) <br />[P, E(10), 1(20)] <br />[P, E&L(5), 1(10)] <br />5,001 - 30,000 <br />P, E(20) <br />or <br />or <br />(18,931-113,562 liters) <br />[P, E(5), L(10)] <br />[P, L(1), E(5)] <br />30,001 - 50,000 <br />P, E(20) <br />P, E&L(5), 1(15) <br />P, E&L(5), 1(10) <br />(113,566-189,271 liters) <br />Portable Containers <br />P <br />P <br />P** <br />Also, when each tank is taken out of service for material repairs, Cecchini Trucking will <br />consult with a qualified tank professional who will determine the following: <br />• The type of integrity inspection that will be conducted (i.e., visual or other non- <br />destructive method), <br />