Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: x Tank Manufacturer ❑Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure x Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Dwyer Manometer Equipment Resolution: +/-2% <br /> Is Tank Exempt From Testing?' ❑Yes x No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 10,000 <br /> Tank Material: Fiberglass <br /> Tank Manufacturer: Unknown <br /> Product Stored: Waste Water <br /> Wait time between applying <br /> pressure/vacuum/water and 30 min 30 min 30 min 30 min <br /> starting test: <br /> Test Start Time: 10:00 <br /> Initial Reading(Rl): 8.35 <br /> Test End Time: 11:00 <br /> Final Reading(RF): 8.33 <br /> Test Duration: 1 hour 1 hour 1 hour 1 hour <br /> Change in Reading(RF-Rl): .02 <br /> Pass/Fail Threshold or Criteria: No less than 1" No less than 1" No less than 1" No less than 1" <br /> Test Result: x Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑Fail <br /> Was sensor removed for testing? x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes ❑No ❑NA <br /> Was sensor properly replaced and x Yes ❑No ❑NA x Yes ❑No ❑NA x Yes []No ❑NA x Yes ❑No ❑NA <br /> verified functional after testin ? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br /> to tina I('alifnrnia f^AA Titly 7'I Cr>rtinn')ATVWA( l <br />