Laserfiche WebLink
Site Preparatio id Installation InstructionsT <br /> TLS-350 UST Monitoring System <br /> I. EIA RS-232 INTERFACES. 1. Measure the distance from the bottom ofthe tank to the <br /> EIA RS-232 Interface Module provides a 25-pin female top of the probe riser pipe(a). <br /> D-connector for data transmission-direct via a null mo- 2. Measure the distance from the bottom of the probe riser <br /> dem cable or through an external modem and over phone pipe to the top of the probe riser pipe(b). <br /> lines—to a computer, point-of-sale terminal or printing 3. Subtract (b) from (a) to determine the correct tank <br /> device.The RS-232 Interface Module with Auxilliary Port diameter(c). <br /> provides an additional 25-pin female D-connector. <br /> 1. Cable Runs. 4. Make sure the probe length(Dimension"A",Figure 22 <br /> An RS-232 Interface and RS-232 Interface with "Capacitance Probe Dimensions"is correct for the tank <br /> diameter. <br /> Auxilliary Port can be used for direct local attachment <br /> of terminals if the cable run is no more than 60 feet.In <br /> practice, runs longer than 60 feet have performed <br /> satisfactorily.However,since the RS-232 specification PROBE RISER PIPE <br /> restricts operation to up to 50 feet,direct-connect cable TANK <br /> ' runs greater than 50 feet are not warranted for proper <br /> operation. b <br /> 16 CAUTION:RS-232 CABLE RUNS LONGERTHAN <br /> 50 FEET COULD RESULT IN DATA ERRORS,OR a <br /> COMPONENT DAMAGE OR BOTH. <br /> a-b=c <br /> 2. Peripheral Equipment Requirements. <br /> Any peripheral equipment connected to an RS-232 <br /> serial port must meet the following criteria: <br /> a. Peripheral equipment must be UL listed. Figure 21. Tank Diameter Measurement. <br /> b. The equipment must have an EIA standard RS-232C <br /> or RS-232D communications protocol. �- A LENGTH OF PROBE <br /> c. The equipment must NOT be installed over or in a (Tank i o> <br /> hazardous location. 17 4' (1.22 m) <br /> J. SITEFAX FAXIMODEM AND INTERNAL 5' (1.52 m) <br /> 5'4" (1.62 m) <br /> MODEM INTERFACES. 6' (1 83 m) <br /> The SiteFax Fax/Modem and the 300/1200-baud Internal 2.0 m <br /> Interface Modem rove snap-in idirect d 7' (2.13 m) <br /> P P-n jacks for data 7'6" (2.28 m) <br /> transmission over phone lines. 8' (2.44 m) <br /> 1. For connection to telephone equipment subject to local 2.5 m <br /> regulations 9' (3 0 m) <br /> 3.0 m <br /> 2. Maximum short circuit current: 0 amps 10' (3.05 m) <br /> 3. Maximum open circuit voltage: 0 volts 11' (3.20 m) <br /> (3.35 m) <br /> L 3.5 m <br /> SECTION 5. CAPACITANCE PROBE <br /> INSTALLATION Figure 22. Capacitance Probe Dimensions. <br /> WARNING: TO PROTECT YOURSELF AND B. RISER PIPE CAP PREPARATION. <br /> OTHERS FROM BEING STRUCK BY VE- <br /> HICLES DURING WORK, BLOCK OFF YOUR The riser pipe cap must have a 3/8" tapped hole for <br /> WORK AREA DURING INSTALLATION AND passage of probe wires.Cap kits with pre-drilled holes for <br /> SERVICE. a standard 4" riser pipe are available from Veeder-Root. <br /> Order Kit Number 312020-952,one for each probe. <br /> WARNING:TO AVOID ELECTRICAL SHOCK <br /> WHICH COULD KILL YOU, BE SURE AC If a kit has not been ordered, perform the following: <br /> POWER TO THE TLS-350 MONITOR IS OFF WARNING: DO NOT PERFORM DRILLING <br /> ih <br /> DURING INSTALLATION. AND TAPPING PROCEDURES IN A HAZARD- <br /> A.TANK DIAMETER MEASUREMENT. OUS AREA. DRILLING AND TAPPING CAN <br /> Perform the following procedure to ensure that probes are CAUSE SPARKS AND IGNITE VOLATILE <br /> installed in the proper tanks(see Figure 21,"Tank Diam- FUMES AND LIQUIDS FOUND IN A CLASS I, <br /> eter Measurement"). Inaccurate readings will result if GROUP DHAZARDOUS LOCATION.FAILURE <br /> probes are not the correct length for the given tank TO COMPLY COULD RESULT IN DEATH,SE- <br /> diameter. RIOUS PERSONAL INJURY, PROPERTY <br /> LOSS AND EQUIPMENT DAMAGE. <br /> 21 <br />