My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_1996 - 2004
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
M
>
MORELAND
>
7700
>
2300 - Underground Storage Tank Program
>
PR0231819
>
COMPLIANCE INFO_1996 - 2004
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/12/2020 5:51:58 PM
Creation date
2/12/2020 10:13:49 AM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
1996 - 2004
RECORD_ID
PR0231819
PE
2351
FACILITY_ID
FA0003732
FACILITY_NAME
99 SHELL*
STREET_NUMBER
7700
STREET_NAME
MORELAND
STREET_TYPE
ST
City
STOCKTON
Zip
95212
APN
13003010
CURRENT_STATUS
01
SITE_LOCATION
7700 MORELAND ST
P_LOCATION
99
P_DISTRICT
003
QC Status
Approved
Scanner
KBlackwell
Tags
EHD - Public
Jump to thumbnail
< previous set
next set >
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
419
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Fv Site Preparation and Insta ,ion Instructions <br /> TLS-350 UST Monitoring System <br /> G. EXTERNAL INPUT WIRING. 1. The Pump Sense Interface Module comes with a con- <br /> The„TLS-350 can accept a dry-contact switch closure nector in place.The connector provides screw termina- <br /> input from an external device such as a line leak detector tions for switch inputs and AC controls. Do not re- <br /> or well monitoring system.Each UO Combination Module move the connector from the module or remove <br /> accepts two inputs. the module from its slot in the monitor during <br /> wiring. Terminal identifications appear only on the <br /> IMPORTANT: ONCE EXTERNAL INPUTS HAVE BEEN module bracket. Removing the connector from the <br /> CONNECTED TO OUTSIDE DEVICES AND THE SYS- module increases the risk of wiring errors. <br /> TEM HAS BEEN STARTED AND PROGRAMMED, <br /> MODULE POSITIONS, CONNECTOR POSITIONS 2. Label all connectors using the self-adhesive labels <br /> AND WIRE POSITIONS CANNOT BE CHANGED supplied according to the slot in which the modules are <br /> WITHOUT REPROGRAMMING THE SYSTEM! installed. <br /> IMPROPER SYSTEM OPERATION WILL RESULT IF 3. Record the location(i.e.,Tank#1,Tank#2,etc.)of each <br /> ANY ONE OF THESE POSITIONS IS CHANGED pump controller wired to a module on the circuit direc- <br /> WITHOUT REPROGRAMMING. tory located inside the TLS-350 door. <br /> Be sure to accurately record on the circuit directory the CAUTION: ONCE PUMP SENSE WIRING HAS ' <br /> type of module,and the location of each device wired to the BEEN CONNECTED AND THE SYSTEM HAS <br /> connector. BEEN PROGRAMMED,MODULE CONNECTOR <br /> Identify each connector with a self-adhesive number label AND WIRING POSITIONS CANNOT BE <br /> according to the slot number. CHANGED WITHOUT RE-PROGRAMMING THE <br /> SYSTEM. <br /> 1. For each external input, connect a shielded cable <br /> consisting of two 18 AWG conductors to the appropri- IMPROPER SYSTEM OPERATIONS WILL RE- <br /> ate terminals on the output module (see Figure 19, SULT IF ANY ONE OF THESE POSITIONS IS <br /> "UO Combination Module Wiring Diagram"). CHANGED WITHOUT RE-PROGRAMMING. <br /> 2. Ground the cable shield to the ground terminal closest 4. Connect the two(2)color-coded or marked wires from <br /> to the conduit entry. Do not ground both ends of the the pump controls to the proper terminals on the Pump <br /> shield on the cable run. Sense Interface Module connector(see Figure 20,"Pump <br /> Sense Module Wiring Diagram"). <br /> I.PUT►�'T'� <br /> r.--z'T'b�-IIEUIT IMPORTANT: BE SURE TO MAINTAIN THE COR- <br /> 0 <br /> RECT CIRCUIT ORIENTATION BETWEEN THE <br /> J vn noau ( COLOR-C ODEDORMAR.KEDFIE LDWIRES AND <br /> CONNECTOR TERMINALS DURING WIRING. <br /> MODULE NOTE:For complete Pump Sense Module installa- <br /> NOT USED tion instructions and wiring diagrams, refer to <br /> 000000, (00 CONNECTOR Veeder-Root Manual No. 576013-822. <br /> GROUND LUG <br /> CLOSEST TO <br /> CONDUIT EHTRV I I i <br /> \ I <br /> \+ I I I I I <br /> _ Ijl II <br /> PUMP <br /> I I I � irul MmE. <br /> m rsc <br /> I I I I I ssvw <br /> CONN IID I I I MONITOR O PUAtPs woouL[ O <br /> I I I I I <br /> L <br /> I I I I <br /> MODULE <br /> \1 \l I \ IIE \ I / <br /> IAWUTINPVT (EXTERNAL EXTERNAL r <br /> ISNiELGED CABLE51 i GEviCE GENGEF CONNECTOR <br /> X000 0001�'i0 <br /> EXTERNAL INPUT I RELAY WTPVT <br /> WIRING.n AWG , WIRINO.I.AWO <br /> Figure 19. UO Combination Module Wiring Diagram. <br /> H. PUMP SENSE INTERFACE MODULE WIRING <br /> CONNECTIONS. <br /> RIGID <br /> WARNING: TO AVOID ELECTRICAL SHOCK CONDUIT) UP Toa MONITOR <br /> n PUMP i <br /> WHICH COULD KILL YOU, BE SURE AC = CONTROLS z <br /> a � a , <br /> POWER TO THE TLS-350 MONITOR IS OFF = <br /> BEFORE OPENING THE FRONT-PANEL AND o� <br /> INSTALLING OR WIRING ANY EXPANSION co� <br /> MODULE. IF HIGH VOLTAGE IS SHORTED <br /> ACROSS ANY BARRIER TERMINAL, EXPLO- <br /> SION AND FIRE COULD RESULT. Figure 20. Pump Sense Module Wiring Diagram. <br /> 20 <br />
The URL can be used to link to this page
Your browser does not support the video tag.