F:V, Preparation and Inst tion Instructions <br /> TIS-350 UST Monitoring System <br /> 16 CAUTION: HANDLE PROBES CAREFULLY! 30A) since they pass from a Class I, Division I or <br /> STRIKING OR DROPPING PROBE WILLRESULT Division 11 area into a non-hazardous area. <br /> IN LOSS OF CALIBRATION AND COULD CAUSE <br /> PERMANENT DAMAGE. <br /> WEATHERPROOF <br /> JUNCTION BOX <br /> 4. Attach the probe cable connector to the mating plug on (t PER PROBE) <br /> the top of the probe.Be sure the connector is attached 1/2'RIGID <br /> securely by hand tightening the locking ring. CONDUIT y BIK <br /> 5. Place floats at bottom of probe before standing the TO FROM <br /> probe on end. MONITOR PROBE <br /> 16 CAUTION: HANDLE PROBES CAREFULLYI <br /> STRIKING ORDROPPING PROBE WILLRESULT + Wh' <br /> IN LOSS OF CALIBRATION AND COULD CAUSE <br /> PERMANENT DAMAGE. <br /> Figure 41. Two-Wire Probe Field Wiring Installation Diagram <br /> 6. Carefully lower probe into the riser pipe until the boot 12. Seal wire nuts with epoxy sealant furnished with <br /> rests on the bottom of the tank. each probe, using one bag for two wire nut connec- <br /> 16 CAUTION.DO NOT ALLOW PROBE TO FREEFALL tions. (Refer to Figure 26, "Epoxy Sealant for Two- <br /> SHARPLY IMPACT THE BOTTOM OF THE Wire Connections.") <br /> TANK SHOCK TO THE PROBE FOOT WILL RE- CAUTION: IF MORE THAN TWO WIRE NUT <br /> SULT IN SEVERE PROBE DAMAGE. CONNECTIONS SHARE AN EPDXY SEALANT <br /> 7. Cut a length of flexible conduit leaving enough slack BAG, THE CONNECTIONS WILL RESULT IN <br /> to remove the riser cap. INACCURATE PROBE READINGS AND POSSI- <br /> 8. Remove cable bushing nut. Feed the two-wire probe BLY FALSE ALARM CONDITIONS. <br /> cable up through the riser pipe cap bushing and WARNING: EPDXY SEALANT MAY BE IRRI- <br /> adaptor.(See Figure 40,"Riser Pipe Cap Bushing and TATING TO EYES AND SKIN. MAY CAUSE <br /> Adaptor.") SKIN SENSITIZATION IN SUSCEPTIBLE IN- <br /> DIVIDUALS.MAY BE ABSORBED THROUGH <br /> THE SKIN.EPDXY SEALANT CONTAINS EP- <br /> FLEXIBLE METAL CONDUIT N." OXY RESIN AND VINYL CYCLOHEXENE DI- <br /> (SUPPLIED WITH AST KIT) OXIDE.VINYL CYCLOHEXENE DIOXIDE HAS <br /> 2 WIRE CABLE CAUSED SKIN CANCER IN ANIMAL TESTS. <br /> STRAIGHT LIOUID7IGHT (SUPPLIED WITH PROBE) <br /> (SUPPLIED WITTHH AST KIT) <br /> CONNECTOR PRECAUTIONS:AVOID EYE AND SKIN CON- <br /> TACT. WEAR IMPERVIOUS GLOVES AND <br /> SAFETY GLASSES.USE ONLY IN WELL VEN- <br /> ADAPTER <br /> (SUPPLIED WITH AST KIT) TILATED AREAS. <br /> REMKE CORD GRIP TVP RSR6 <br /> (SUPPLIED WITH PROBE) <br /> 13. Tighten the cable bushing nuts on the probe riser cap <br /> o and junction box to ensure a water-tight seal at the <br /> probe cable entry. (See Figure 42, "Junction Box <br /> Liquidtight Connector.") <br /> 14. Secure the riser locking cap to the top of the riser pipe. <br /> A padlock may be installed for added security. <br /> Figure 40. Riser Pipe Cap Bushing and Adaptor <br /> 9. Connect the adaptor to the cable bushing but do not <br /> tighten. <br /> 10. Continue to feed the cable through the conduit and <br /> conduit connectors. Leave enough slack in the cable J-BOX <br /> between the cap and junction box to allow the cap to _ <br /> easily reach the riser pipe.In addition,leave enough -- <br /> slack under the riser cap to allow the probe to rest on ----- ---- <br /> the bottom of the tank. <br /> STRAIGHT LIOUIDTIGHT <br /> 11. Using wiring nuts,connect wires from the probe cable CONNECTOR,W' <br /> to the probe field wires in the junction box(see Figure (SUPPLIED WITH AST KIT) <br /> 41). Be sure to observe proper polarity between the <br /> probe and monitor wiring during installation. The <br /> conduit must be properly sealed in accordance with <br /> the National Electrical Code (NFPA 70) and the <br /> Automotive and Marine Service Station Code(NFPA Figure 42. Junction Box Liquidtight Connector <br /> 28 <br />