Laserfiche WebLink
Site Preparation. 1 Installation Instructions <br /> TLS-350 UST Monitoring System <br /> Fl <br /> b. Remove one of the plugs from the top of the junction NOTE:The mounting sleeve must be mounted far <br /> box, 16 enough into the sump to allow the sump sensor, <br /> c. Position the mounting bracket on top of the junction when installed,to rest on the base of the sump and <br /> box aligningthe holein the bracketwith the threaded be mounted at least one inch up from the base. <br /> hole in the box. b. Mark a line on the sump wall indicating the top of <br /> d. Install and slightly tighten the cord grip to hold the the mounting sleeve. <br /> mounting bracket in position. Turn the bracket so c. Apply cement approved for use with PVC and the <br /> the mounting sleeve is as close to the outer sump sump wall material generously in a line running the <br /> wall as possible and fully tighten the cord grip. complete length of the sleeve. <br /> e. If necessary,carefully bend the mounting bracket so d. Using a level, position the sleeve vertically at the <br /> that the mounting sleeve is in a true vertical posi- mark indicated on the sump wall and press it firmly <br /> tion. Using a level, check the mounting sleeve to to the side of the sump.BE SURE THE SLEEVE IS <br /> confirm that it is vertical. VERTICAL. <br /> f. Carefully slide the sump sensor into the mounting e. Hold the sleeve in position until the cement has <br /> sleeve until it rests on the sump base. hardened. <br /> g. Feed the leader cable through the cord grip on the f. Install and connect the sump sensor following the <br /> junction box. <br /> instructions in Section 9.B.3.f. through 9.B.3.j. <br /> h. Tighten the cord grip nut to ensure a water-tight SECTION 10. VAPOR SENSOR <br /> seal at the cable entry. INSTALLATION <br /> i. Using wire nuts, connect the two-wire cable to the WARNING:HIGH VOLTAGES ARE PRESENT <br /> field wires in the sensor junction box(see Figure 44, IN THESE SYSTEMS. TAKE PRECAUTIONS <br /> "Two-Wire Float-Switch Sensor Field Wiring Dia- TO PREVENT PERSONAL INJURY, PROP- <br /> gram").Since these are contact switches,polarity is ERTYLOSS AND EQUIPMENT DAMAGE.DIS- <br /> not a consideration when connecting sensor wires to CONNECTAC VOLTAGE AND TURN OFFALL <br /> field wires. LINE POWER BEFORE REMOVING AND RE- <br /> PLACING ANY PARTS. <br /> j. Seal wire nuts with epoxy sealant using one bag for <br /> two wire nut connections. (Refer to Figure 26,"Ep- TO AVOID ELECTRICAL SHOCK WHICH <br /> oxy Sealant for Two-Wire Connections.") COULD KILL YOU, BE SURE AC POWER TO <br /> THE SYSTEM IS OFF DURING SERVICE. <br /> 16 CAUTION: IF MORE THAN TWO WIRE NUT <br /> CONNECTIONS SHARE AN EPDXY SEALANT WARNING: A VEEDER-ROOT VAPOR SEN- <br /> BAG,THE CONNECTIONS WILL NOT BE PROP- SOR SHOULD BE INSTALLED ONLY IN <br /> ERLY SEALED. IMPROPER SEALING OF THE WELLS WHERE: <br /> CONNECTIONS WILL RESULT IN INACCURATE PRELI IINARYTESTING HAS DETER, <br /> SENSOR READINGS AND POSSIBLY FALSE MINED THAT THE SOIL IS NOT CON- <br /> ALARM CONDITIONS. TAMINATED BEYOND ACCEPTABLE <br /> 12 WARNING: EPDXY SF-41—ANT MAY BE IRRI- LIMITS,OR <br /> TATING TO EYES AND SKIN. MAY CAUSE WHERE CONTAMINATED SOIL HAS <br /> SKIN SENSITIZATION IN SUSCEPTIBLE IN- BEEN REMEDIATED AND IS NOW <br /> DIVIDUALS.MAY BE ABSORBED THROUGH CLEAN, <br /> THE SKIN.EPDXY SEALANT CONTAINS EP- <br /> OXY RESIN AND VINYL CYCLOHEXENE DI- A VAPOR SENSOR SHOULD NOT BE IN- <br /> OXIDE.VINYL CYCLOHEXENE DIOXIDE HAS STALLED IN WELLS WHERE PRELIMINARY <br /> CAUSED SKIN CANCER IN ANIMAL TESTS. TESTING INDICATES THAT THE INITIAL <br /> VAPOR SENSOR RESISTANCE EXCEEDS 26k <br /> PRECAUTIONS:AVOID EYE AND SKIN CON- OHMS. <br /> TACT. WEAR IMPERVIOUS GLOVES AND <br /> PROD- <br /> SAFETY GLASSES.USE ONLY IN WELL VEN- CAUTION: ONLY INSTALL THIS PROD- <br /> S <br /> SAFTED AREAS. 16UCT IN WELLS WHERE PRELIMINARY TEST- <br /> ING HAS DETERMINED PRESENT VAPOR LEV- <br />.jft 4. To mount the sump sensor by cementing the PVC ELS TO BE ACCEPTABLE FOR ITS USE. <br /> mounting sleeve to the sump wall (fiberglass sumps <br /> only) (see Figure 55, "Mounting Sleeve Cemented to WARNING: TO PROTECT YOURSELF AND <br /> Sump Wall"): 12 OTHERS FROM BEING STRUCK BY VE- <br /> HICLES DURING WORK,BLOCK OFF YOUR <br /> a. Select a position for the mounting sleeve in the sump WORK AREA DURING INSTALLATION AND <br /> as far away from the submersible pump as possible. SERVICE. <br /> 35 <br />