i <br /> I <br /> located in the parking area to the north of the containment area. The holes in the berm wall do not <br /> have valves to prevent rainwater or product from flowing from the berm. Additionally,there is a <br /> portion of the berm wall near the pump that is not continuous which would allow product to leave <br /> the berm in the event of a release.Apex recommends installing valves on the drain holes and <br /> completing the berm wall near the pump to prevent product from flowing out of the berm in the event <br /> of a release. The SPCC Plan must be amended following the installation or modification of any <br /> secondary containment structure. <br /> I <br /> When a valve is installed, the valve must be kept in the closed position, except when draining the <br /> secondary containment berms. The content of the secondary containment berms must be inspected by <br /> facility personnel prior to draining to ensure that only oil-free water is allowed to enter the facility storm <br /> water drainage system. After the inspection verifies that only oil-free water will be released,the bypass <br /> valve will be opened and the accumulated water will be released under direct and continuous <br /> supervision. 0 <br /> Drainage events are recorded in the log included in Attachment to this SPCC Plan and must be <br /> kept with the Plan for at least 3 years. <br /> I <br /> COMPLETELY BURIED TANKS (40 CFR 112.8(c)(4)) <br /> There are two USTs at the subject site. Two of the USTs are located near the convenience store <br /> building: a 10,000-gallon regular gasoline UST and a 20,000-gallon UST split into three <br /> compartments. The compartments include a 12,000-gallon regular gasoline compartment, a 4,000- <br /> gallon diesel compartment and a 4,000-gallon premium gasoline compartment. The remaining UST is <br /> a 6,000-gallon tank containing DEF that is located to"the west of the diesel dispenser canopy. The <br /> USTs are exempt from the requirements of the SPCgulations as they are properly permitted with <br /> the local permitting agency. r� <br /> PARTIALLY BURIED TANKS (40 CFR 112.8(c)(5)) <br /> There are no partially buried tanks at the facility as defined in 40 CFR 112.2. <br /> PERIODIC INTEGRITY TESTINO(40 CFR 112.8(c)(6)) <br /> Visual inspections of ASTs by facility personnel are performed according to the procedure described in <br /> this SPCC Plan. Leaks from tank seams, gaskets, rivets, and bolts are promptly corrected. Records of <br /> inspections and tests are signed by the inspector and kept at the facility for at least five years. <br /> i <br /> Periodic Integrity testing at the facility should be performed in accordance with the Steel Tank Institute <br /> (STI) Standard for the Inspection of Aboveground Storage Tanks, SP-001,2011. The scope and <br /> schedule of certified inspections required by the STI SP-001 2011 standard varies based on the size and <br /> category of the tanks. All tanks at the site are single walled tanks with spill control and release <br /> prevention barriers as defined in the SP-001 standard;therefore,the tanks at the site are classified as <br /> Category 1 tanks. The scope and schedule of each tank is summarized in the table below. Descriptions <br /> for each inspection are included below. j <br /> I <br /> Joe's Travel Plaza <br /> 15600 Harlan Road,Lathrop,CA <br /> Page 18 <br />