SAN.JOARIN Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Nene: I Facility Address: Date: <br /> JOES TRAVEL PLAZA 15600 SHAR LAN RD, LATHROP February 13, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Ntaicem Comply) <br /> Item M Remarks <br /> 613 CFR 112.7(c)Failure to provide appropriate secondary containment,diversionary structures or equipment. <br /> How the buried piping is provided appropriate containment and/or diversionary structures or equipment to prevent a <br /> discharge is not described in the SPCC plan. The diesel tank loading area is described as having a roll over berm <br /> to provide appropriate containment in the event of a release.The bermed area appears to not be capable of <br /> containing liquid.The southwest corner of the berm is missing and there are cuts on the berm in several areas. <br /> Provide appropriate containment and/or diversionary structures or equipment to prevent a discharge as described in <br /> §112.1(b),except as provided in paragraph(k)of this section for qualified oil-filled operational equipment,and <br /> except as provided in§112.9(dx3)for flowlines and intra-facility gathering lines at an oil production facility.The <br /> entire containment system,including walls and floor,must be capable of containing oil and must be constructed so <br /> that any discharge from a primary containment system,such as a tank,will not escape the containment system <br /> before cleanup occurs. In determining the method,design,and capacity for secondary containment, you need only <br /> to address the typical failure mode,and the most likely quantity of oil that would be discharged.Secondary <br /> containment may be either active or passive in design.At a minimum,you must use one of the following prevention <br /> systems or its equivalent: <br /> (1)For onshore facilities: <br /> (i)Dikes, berms,or retaining walls sufficiently impervious to contain oil; <br /> (ii)Curbing or drip pans; <br /> (iii)Sumps and collection systems; <br /> (iv)Culverting,gutters,or other drainage systems; <br /> (v)Weirs,booms,or other barriers; <br /> (vi)Spill diversion ponds; <br /> (vii)Retention ponds;or <br /> (viii)Sorbent materials. <br /> (2)For offshore facilities: <br /> (i)Curbing or drip pans;or <br /> (ii)Sumps and collection systems. <br /> Provide appropriate containment and/or diversionary structures or equipment to prevent a discharge.You need only <br /> to address the typical failure mode,and the most likely quantity of oil that would be discharged.Secondary <br /> containment may be either active or passive in design.An an amendment to this section of the SPCC plan may <br /> require certification by a Professional Engineer. <br /> This is a minor violation. <br /> FM000174 PR0E15GM 50001 0213202t <br /> EHD18-01 Rcr.&2N1018 Page 5 of Abaveg JPtl —SWr AC OIR <br /> 1868 E. Hazelton Avenue I Stockton,California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />