Laserfiche WebLink
SAN. JOARIN Environmental Health Department <br /> COUNTY <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Nan.: I Facility Address: Date: <br /> JO ES TRAVEL PLAZA 15600 SHAR LAN RD, LATHROP February 13, 2020 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Naic.m Comply) <br /> Item M Remarks <br /> 706 CFR 112.8(cx2)Failed to provide and maintain adequate secondary containment. <br /> The 10,000 gallon diesel tanks appeared to be permanently manifolded and this is not addressed in the SPCC plan. <br /> THe SPCC plan states in one section that the 10,000 gallon tanks are single walled and states in another section <br /> that the tanks are double walled. <br /> Construct all bulk storage tank installations(except mobile refuelers and other non-transportation-related tank <br /> trucks)so that you provide a secondary means of containment for the entire capacity of the largest single container <br /> and sufficient freeboard to contain precipitation.You must ensure that diked areas are sufficiently impervious to <br /> contain discharged oil. Dikes,containment curbs,and pits are commonly employed for this purpose.You may also <br /> use an alternative system consisting of a drainage trench enclosure that must be arranged so that any discharge will <br /> terminate and be safely confined in a facility catchment basin or holding pond. <br /> The SPCC plan must address secondary containment requirements for all tanks as required by regulations.The <br /> professional Engineer must certify that an permanently manifolded tanks have sufficient secondary containment. <br /> Note: Permanently manifolded tanks are tanks that are designed, installed,or operated in such a manner that the <br /> multiple containers function as a single storage unit(67 FR 47122,July 17, 2002).Accordingly,the total capacity of <br /> manifolded containers is the design capacity standard for the sized secondary containment provisions(plus <br /> freeboard in certain cases). <br /> This is a Class II violation. <br /> FM000174 PR0515GM 50001 02132021 <br /> IND18-0111-9 N1019 Page 6 of Abaveg JPtl —SWr AC OR <br /> 1868 E. Hazelton Avenue I Stockton,California 95205 1 T 209 468-3420 1 F 209 4840138 1 wwwajoehd.com <br />