Laserfiche WebLink
08/21/1997 13 53 818-840-6929 TRIANGLE ENVIRO INC PAGE 02 <br /> i • <br /> Triangle Environmental, Inc. <br /> 7,525 West Burbank Boulevard,Burbank,California 91505 <br /> (818)840-7020 FAX(818)840-6929 <br /> T.E.I. UST TESTING SYSTEMS S UMMAR Y SHEET <br /> Precision Underground Storage Tank System. Leak Test <br /> Client, <br /> TOSCO MARKETING COMTANY Unocal #31010 <br /> 3550 N Central Ave ,4th Floor <br /> Phoenix, AZ 85012 Test Date: 7/21/97 <br /> Carmen Tucker <br /> (602)200-4530 <br /> Facility Work#. 460084 <br /> Unocal #31010 County: <br /> 2701 W MARCH LN Cross Street. <br /> STOCKTON, CA 952070000 <br /> q.IIY I.YI II I.I IY <br /> I II IIY .i, <br /> Tattle Test System Tank Linc ' <br /> # Product Capacity Type Rate/Results UlIage Result Ratc/Result LID Result <br /> .YIY III 1111 <br /> li. .YYYYi.YI <br /> 1 Unleaded Regular 15000 System 5000 0 02 PASS PASS 0 000 PASS PASS <br /> . 2 Unleaded Premium 15000 System 5000 0 02 PASS PASS 0 000 PASS PASS <br /> 3 Diesel 12000 System 5000 0 02 PASS PASS 0 000 PASS PASS <br /> Certified By Technician, James Bowen State Lie.#s. CA-97-1603 <br /> 4Mfgr's#: TEI.053 CO-0547A 1D-9634006 <br /> � <br /> KFCK-98212 AZ-T00033 <br /> Com inents. <br /> Compliance Tanks All,Monitor Certification <br /> r <br /> I <br /> This precision tank testing system bas been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0 10 <br /> gph with a Pd>95%and Pfa<5% as required by Local,State and Federal EPA UST Technical Standards <br /> Part 280 for precision testing systems <br />