Laserfiche WebLink
06/21/1997 13 53 818-846-6929 TRIANGLE ENVIRO INC PAGE 03 <br /> i Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Unocal #31010 <br /> Tank #: 1 Test Date: 7/21/97 <br /> Product: Unleaded Regular Work#- 460084 <br /> Test Method System 5000 Test Method R J FTA <br /> Capacity 15000 Manufacturer Vaporless <br /> Diameter(in) 107 L/D Model LD-2000 <br /> Product Level(in) 69 LID Serial# 47634 <br /> Liquid Volume(Gals) 9$$6 Line Drain Back(ml) 150 <br /> Liquid Percent(%) 659% LID Trip Tame(sec) 3 <br /> Specific Gravity 0 750 Holding Pressure(psi) 14 <br /> Cod of Expansion 4 000b50 Metering Pressure(psi) 29 <br /> Water On Tank(in) 0 LID Test Rate(gph) 17 <br /> Water In Tank(in) 0 L/D Result PASS <br /> Product'T'emp (F) 83 <br /> Head Pressure(psi) 19 HEEMM <br /> Test Start Time 10 30 00 PM <br /> Test End Time 10 45 00 PM Test Method TEI LT-3 <br /> Test Rate(gph) 002 Pump Brand Red Jacket <br /> Test Result PASS System Type Pressure <br /> Line Pressure(psi) 50 <br /> IMMIEMME= Line Start Time 9 00 00 PM <br /> Test Method ULLAGE Lune End Time 9 15 00 PM <br /> UllageVolume(gals) 5114 Line Start Level 60 <br /> Ullage Test Tine 10 30 00 PM Line Enid Level 60 <br /> Ullage Vacuum(psi) 29 Line Test Rate(gph) 0 000 <br /> Ullage Result PASS lane Test Result PASS <br /> 1 <br /> 2 <br />