Laserfiche WebLink
OB/21/1997 13 53 818-840-6929 TRIANGLE ENVIRO INC PAGE 04 <br /> w <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Unocal #31010 <br /> Tank#: 2 Test Date: 7/21/97 <br /> Product: Unleaded Premium Work 4: 460084 <br /> Test Method System 5000 Test Method R.J FTA <br /> Capacity 15000 Manufacturer Vaporless <br /> Diameter(in,) 107 L/D Model LD-2000 <br /> Product Level(in) 56 LID Serial# 47632 <br /> Liquid Volume(Gals) 7643 Line pram Back(ml) 160 <br /> Liquid Percent(%) 510% LID Trap Time(sec) 2 <br /> Specific Gravity 0 750 Holding Pressure(psi) 15 <br /> Coef of Expansion 0000650 Metering Pressure(psi) 28 <br /> Water On,Tank(in) 0 LID Test Rate(gph) 19 <br /> Water In Tank(in) 0 L/D Result PASS <br /> Product Temp (F) 80 <br /> Head Pressure(psi) 15 <br /> Test Start Time 10 50 00 PM <br /> Test End Tune 11 00 00 PM Test Method TEI LT-3 <br /> Test Rate(gph) 002 Pump Brand Red Jacket <br /> Test Result PASS System Type Pressure <br /> Line Pressure(psi) 50 <br /> Line Start Tune 9 00 00 PM <br /> Test Method ULLAGE Lirie End Tune 9 15 00 PM <br /> UllageVolume(gals) 7357 Line Start Level 130 <br /> Ullage Test Tune 10 50 00 PM Lune End Level 130 <br /> Ullage Vacuum(psi) 25 Line Test Rate(gph) 0 000 <br /> Ullage Result PASS Lime Test Result PASS <br /> 3 <br />