Laserfiche WebLink
D. Results of Testing/Servicing <br /> Software Version Installed: 329.01 <br /> Com tete the following checklist: <br /> ® Yes ❑ No' Is the audible alarm operational? <br /> ® Yes ❑ No' Is the visual alarm operational? <br /> ® Yes ❑ No' Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> ® Yes ❑ No` Were all sensors installed at lowest point of secondarl containment and positioned so that other equipment will not interfere with their proper <br /> operation? <br /> El Yes ❑ No' If alarms are relayed to a remote monitoring station,is II communications equipment(e.g.,modem)operation I1 <br /> ® N/A <br /> ® Yes El No* For pressurized piping systems,does the turbine automatically shut down if the piping secondary containmen monitoring system detects a leak, <br /> ❑ N/A fails to operate, or is electrically disconnected? If yes: which sensors initiate positive shut-down? (Chec all that apply) ® SumpfTrench <br /> Sensors; ®Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and st nsor failure/disconnection? to Yes; ❑No. <br /> ❑ Yes ❑ No' For tank systems that utilize the monitoring system as the primary tank overfill warning device(i.e., no me hanical overfill prevention valve is <br /> ® N/A installed),is the overfill warning alarm visible and audi Die at the tank fill point(s)and operating properly? Ifo,at what percent of tank capacity <br /> does the alarm trigger? 0% <br /> ❑ Yes ® No Was any monitoring equipment replaced? If yes,Iden ify specific sensors,probes,or other equipment replaced and list the manufacturer name <br /> and model for all replacement parts in Section E,below. <br /> ❑Yes' ® No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply <br /> ❑Product; ❑Water. If yes,describe causes in Sect on E,below. <br /> ® Yes ❑ No' Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ® Yes ❑ No' Is all monitoring equipment operational per manufactur is specifications? <br /> In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: LITTLE DRIPS OF WATER IN SUMPS INS ECTOR TOOK PICS <br /> Monitoring System Certification Page 2 of 4 2/21/07 <br />