Laserfiche WebLink
NOTES: <br />A. ALL WIRING TO BE PER MANUFACTURERS WIRING <br />DIAGRAMS. <br />B. VENDOR #2 SHALL WIRE SMOKE DETECTORS TO <br />FIRE ALARM SYSTEM UNDER THE ELECTRICAL <br />CONTRACTOR'S SCOPE OF WORK, PER SITE <br />SPECIFIC CODE REQUIREMENTS. <br />REMOTE KEY TEST SWITCH, INDICATOR LIGHT, AND <br />C• ALARM FURNISHED WITH RTU SHALL BE INSTALLED <br />AND WIRED TO RTU BY MECHANICAL CONTRACTOR. <br />COORDINATE EXACT LOCATION WITH AUTHORITY <br />HAVING JURISDICTION. <br />3 #18 - 1/2"C. <br />PROVIDE LABEL <br />"DUCT DETECTOR IN ALARM" <br />DUCT SMOKE DETECTOR WIRING DETAIL <br />/ NTS <br />THE CONTRACTOR SHALL PROVIDE A FIRE -RATED ENCLOSURE FOR THE KITCHEN <br />EXHAUST DUCTWORK AS SPECIFIED BY CODE. IF APPROVED BY THE CODE <br />AUTHORITY HAVING JURISDICTION, THE CONTRACTOR MAY USE UL LISTED, <br />FIRE -RATED KITCHEN EXHAUST DUCT WRAP IN LIEU OF A GYP <br />BOARD -CONSTRUCTED ENCLOSURE. EXHAUST DUCT WRAP SHALL BE <br />FOIL -ENCAPSULATED, NON-COMBUSTIBLE, INORGANIC, FLEXIBLE FIREPROOFING WRAP <br />AND SHALL BE FYREWRAP 2.0 BY UNIFRAX CORPORATION OR ENGINEER -APPROVED <br />EQUAL. <br />A <br />FIRE ENCLOSURE <br />CLEANOUT ACCESS <br />PANEL AT ALL ELL'S_ <br />ACCESS PANEL— <br />A <br />— WELDED <br />STEEL DUCT <br />16 GA. ALL WELDED STEEL <br />DUCT PER AUTHORITY <br />HAVING JURISDICTION <br />SLOPE 1/4" / FT. OR AS <br />REQUIRED BY THE AUTHORITY <br />CEILING HAVING JU ISDICTION <br />GREASE EXHAUST DUCT DETAIL <br />NTS <br />GREASE DUCT WRAP DETAIL <br />NTS <br />INSTALL FAN <br />CONTROLLER 0 <br />HOUSING AND PF <br />ACCESS TO CONTR <br />3" MIN <br />12" <br />MAX <br />TYPICAL <br />#18 <br />#18 <br />FACTORY INSTALLED SMOKE DETECTORS <br />LOCATED IN THE SUPPLY AND RETURN AIR <br />OPENINGS OF THE RTU WITH SAMPLING TUBES <br />SIZED AS REQUIRED. <br />(TYPICAL OF EACH UNIT) <br />--POWER FROM RTU <br />(FACTORY WIRED) <br />INTERLOCKED TO SHUT <br />DOWN UNIT ON ALARM <br />(FACTORY WIRED) <br />REMOTE KEY TEST SWITCH (SHIPPED LOOSE <br />WITH ROOF TOP UNIT) IN BOX ON COLUMN <br />NEAR DETECTOR <br />SYSTEM SENSOR SHIPPED LOOSE WITH ROOF <br />TOP UNIT. MOUNT IN LOCATION WHERE IT CAN <br />BE HEARD DURING NORMAL OCCUPANCY. <br />SECTION A -A <br />NOTES: <br />OTWO LAYERS OF FIRE RATED DUCT INSULATION <br />OFILAMENT TAPE (TEMPORARY HOLD) <br />O SS BANDING STRAPS (PERMANENT HOLD) <br />O4 3" MINIMUM LOGITUDINAL OVERLAP <br />APPROVED MANUFACTURERS: UNIFRAX FYREWRAP <br />WRAP MUST COMPLY WITH ASTM E2336 <br />SHALL BEGIN <br />)P OF HOOD <br />NDERSIDE OF <br />UGE BLACK STEEL <br />:D EXHAUST DUCT, SEE <br />FOR SIZE. <br />'.nll\t.T.Iill\ <br />CABINET EXAHUST FAN WITH INTEGRAL GRILLE DETAIL <br />NTS <br />UPBLAST ROOF EXHAUST FAN. SEE PLAN <br />FOR LOCATION. PROVIDE ACCESS FROM <br />PROVIDE ACCESS PANEL FOR FAN (TYPICAL) <br />GREASE CONTAINS <br />PROVIDE MANUFACTURER'S <br />RECOMMENDED CURB PROVIDE <br />FLASH & COUNTER FLASH <br />AROUND DUCT PENETRATION <br />(TYPICAL) <br />THE CONTRACTOR SHALL PROVIDE A FIRE -RATED <br />ENCLOSURE FOR THE KITCHEN EXHAUST DUCTWORK <br />AS SPECIFIED BY CODE. IF APPROVED BY THE CODE <br />AUTHORITY HAVING JURISDICTION, THE CONTRACTOR <br />MAY USE UL LISTED, FIRE -RATED KITCHEN EXHAUST <br />DUCT WRAP IN LIEU OF A GYP BOARD -CONSTRUCTED <br />ENCLOSURE. EXHAUST DUCT WRAP SHALL BE <br />FOIL -ENCAPSULATED, NON-COMBUSTIBLE, INORGANIC, <br />FLEXIBLE FIREPROOFING WRAP AND SHALL BE <br />FYREWRAP 1.5 OR 2.0 BY UNIFRAX CORPORATION <br />OR FIREMASTER BY 3M OR ENGINEER -APPROVED <br />SUBSTANTIAL EQUIVALENT <br />16 GAUGE BLACK STEEL DUCT W/ <br />DOORSAS REQUIRED BY CODAC CESS <br />10' MINIMUM <br />BETWEEN INTA <br />AND EXHAUS <br />40" MINIMUM NEMA 3R <br />—{— /F DISCONNECT <br />FILTER <br />KITCHEN HOOD, EXHAUST FAN, AND SUPPLY FAN DETAIL <br />Vi 1 NTS <br />NOTES: <br />1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION. <br />2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR <br />MULTI -BLADE DAMPERS & ROUND DAMPERS. <br />1/2" (15 MM) INSULATION <br />ROUND ROD PIN 1 <br />INSULATION <br />STAND-OFF <br />HANDLE WI1 <br />LOCKING <br />QUADRANT <br />INSIDE END <br />BEARING <br />SECTION <br />VOLUME DAMPER DETAIL <br />NTS <br />END BEARING <br />BLADE <br />INSULATION <br />MM) CLEARANCE <br />ALL AROUND <br />DUCTMATE #CL -10 "CLUTCHER" WIRE <br />ROPE HANGER SYSTEM, SPACED 8' O.C. <br />MAXIMUM FOR SPRIRAL PIPE INTALLED IN <br />10' LENGTHS <br />LOW -RIB SPIRAL DUCT, MINIMUM 26GA <br />EQUIVALENT, GAUGE PER SMACNA <br />CONSTRUCTION STANDARDS <br />RIGID DUCT INSTALLATION <br />i ALTERNATE CADDY -CLIP TYPE FASTENER <br />KITCHEN SUPPLY FAN <br />SEE PLAN FOR LOCATION <br />PROVIDE SUPPLY EXTENSION <br />AS REQUIRED. <br />PROVIDE BIRD SCREEN <br />PROVIDE SUPPORT <br />ROOF <br />COORDINATE STRUCTURAL <br />WITH STRUCTURAL PLAN <br />PROVIDE SUPPORTS (TYPICAL) <br />CEILING - <br />HOODS SHALL HAVE SUPPLY & EXHAUST OPENINGS <br />AS SPECIFIED IN KITCHEN CONSULANT PLANS. PANT <br />LEG THE RESPECTIVE DUCTS TOGETHER AS <br />REQUIRED AND RISE UP TO FAN ON ROOF AS <br />INDICATED ON THE DRAWING. CONTRACTOR SHALL <br />MAKE DUCT CONNECTION AT HOOD COLLARS AT <br />SIZES INDICATED ON KITCHEN CONSULTANT PLANS, <br />CONTROL <br />HOOD SPECIFICATION <br />KITCHEN HOODS WITH INTEGRAL <br />EXHAUST AND SUPPLY COLLARS <br />SHALL BE SUPPLIED UNDER KITCHEN <br />EQUIPMENT CONTRACT. REFER TO <br />KITCHEN DRAWINGS FOR HOOD <br />ELEVATIONS <br />FLOOR <br />SIDE ELEVATION <br />STIFFEN BLADE <br />AS REQUIRED <br />DAMPER BLADE <br />HANDLE WITH <br />LOCKING QUADRANT <br />DUCT <br />MAXIMUM HANGER <br />JANUARY 2018 <br />SPACING ON <br />17-057 <br />SPIN -IN COLLAR WITH DAMPER <br />HORIZONTAL ALR RUNS <br />CHECKED : <br />MAIN SUPPLY DUCT 2 IN. THICK DUCT <br />1• STRAP AND <br />WRAP, 1.OPCF, R-6.0 INSTALLED, FSK <br />CEILING HANGER <br />FOIL FACED JACKET, KNAUF, OWENS <br />WIRE ATTACHED <br />CORNING OR EQUAL <br />TO JOIST ABOVE <br />71 RIGID DUCT <br />ND JOIST OR OTHER SUPPORT IV k <br />,A MINIMUM STRAP, 1 • WIDE, 6' <br />XIMUM HORIZONTAL SPACING SEAL JOINTS IN ROUND RIGID DUCT MINIMUM 2 <br />& AT TAPS WITH MAIN DUCT <br />DIAMETERS <br />USE DRAW BANDS CONNECTION POINTS <br />AT TOP OF DUCT OF FLEXIBLE WITHRI RIGID DUCT dt AT <br />DIFFUSER <br />INSULATE TOP OF DIFFUSER AND <br />REGISTER (JYP.) <br />P UNDER DUCT 1" WITH #8 <br />FLEX DUCT INSTALLATION <br />NTS <br />NOTE: <br />1. METHOD OF INSTALLATION FOR AIRTIGHT SEAL WILL BE TYPICAL <br />FOR ALL FLEX CONNECTIONS TO AIR DISTRIBUTION DEVICES <br />2. INSULATE TOP OF DIFFUSER ABOVE CEILING AS SCHEDULED. <br />LAY -IN CEILING DIFFUSER AND RIGID DUCT INSTALLATION DETAIL <br />/ NTS <br />CEILING DIFFUSER SEE SCHEDULE FOR <br />MODEL. <br />ROUND FLEXIBV DUCT SAME SIZE AS <br />pIFFUSER NEC (6'-0" MAX. LENGTH) <br />UL CLASS i INSULATED DUCT MATERU4, <br />THERMAFLFJC M -KE a INSULATED, R-6.0 <br />INSULATED FLJ DUCT <br />SEAL. AND TAPE OUTER <br />JACKET AT RIGID DUCT AND <br />DIFFUSER NECK <br />4 INCH LONG DUCT COLLAR TYP. <br />FOR ALL CONNECTIONS TO CEILING <br />DIFFUSERS <br />REFER TO ARCHITECTURAL DWGS. FOR <br />CEILING TYPE <br />2018-025 <br />GDMD ENGINEERING, INC <br />Mechanical and Safety Engineers <br />212 W Pine St, Ste 4 <br />Lodi, Ca 95242 <br />Ph 209-367-0899 <br />Fax 209-367-0898 <br />E-mail-.gdmdengrinc@sbcglobal.net <br />api COPYRIGHT 2017 <br />REVISIONS <br />THIS DOCUMENT, AND THE IDEAS AND DESIGNS <br />INCORPORATED HEREIN, AS AN INSTRUMENT OF <br />PROFESSIONAL SERVICE, IS THE PROPERTY OF <br />"api' AND IS NOT TO BE USED, IN WHOLE OR IN <br />PART, FOR ANY OTHER PROJECT WITHOUT <br />WRITTEN AUTHORIZATION. <br />PLANNING ■ ■ ■ <br />ARCHITECTURE ■ ■ ■ <br />al3i <br />ARCHITECTURE PLUS INC. <br />4335-8 NORTH STAR WAY <br />MO D ESTO, CA 95356 <br />ph. 209.577.4661 <br />fx. 209.577.0213 <br />www.apiarc.com <br />FRANK C. BOOTS <br />JOSEPH L. SMITH <br />RODNEY C. ALONZO <br />ARCHITECTS <br />a <br />U <br />J <br />W <br />IV <br />Zz <br />4 <br />U� <br />y � <br />I� y <br />W W <br />Z <br />W <br />1► <br />►77 <br />/S\pNAL F� <br />G. D qL c'ti <br />7k <br />u') REN:60-I8 <br />y� GQ ¢? <br />DATE: <br />JANUARY 2018 <br />JOB NO. ; <br />17-057 <br />DRAWN: <br />A. BARROZO <br />CHECKED : <br />G. DAVIS <br />SHEET <br />z <br />0 <br />SeO <br />N <br />