Laserfiche WebLink
Jimco Truck Plaza - 2 - 5 September 2012 <br /> 1022 E. Frontage Rd. (Hwy. 99) <br /> Ripon, Sari Joaquin County <br /> In May 2C04, one 1,000-gallon waste oil UST and a portion of the associated piping were <br /> removed, while the remaining piping was closed in place. Maximum waste oil UST/piping <br /> confirmation results were TPHd, 17,600 mg/kg; and TPHg, 59.3 mg/kg. <br /> In April 2005, the San Joaquin County Environmental Health Department (SJCEHD) reported <br /> the failure of a coupling from the diesel AGSTs to the piping, and that repairs were underway at <br /> the Site. n response, Regional Board staff conducted a Site inspection and provided a copy of <br /> the inspection memo to the Site Cleanup Section for further evaluation. <br /> From October 1996 through March 2010, forty nine borings (B14 through B16, B-1 through <br /> B-41, CP---1 through CPT-3, HP17 and HP18) were advanced, and twenty monitoring wells <br /> (MW-1 through MW-20) and two remediation wells (EW-1 and AS-1) were installed. <br /> Maximum soil sam le results are reported in milligrams per kilo ram m /k : <br /> Date TPHg TPHd TPHmo B T E X MTBE TBA 1,2-DCA <br /> 10/961 160 1,300 NA 0.11 0.69 <0.005 0.64 0.016 NA NA <br /> 6/98 5,100 13,000 NA 0.19 2.4 17 150 2.0 NA NA <br /> 9/98 1,500 4,700 NA 1.6 46 32 190 14 NA NA <br /> 5/99 1,300 1 8,200 NA 2.6 3.4 1 5.8 39 9.9 1 NA NA <br /> 1/02 71 230 NA <0.005 <0.005 <0.005 <0.01 0.3 <0.01 NA <br /> 5/02 260 800 NA <0.005 <0.005 <0.005 0.99 0.54 <0.025 NA <br /> 5/04 59.3 17,600 NA <0.005 0.022 0.18 0.752 <0.5 <0.5 <0.5 <br /> 8/05 980 250 280 <0.1 0.11 0.72 1.3 0.17 0.25 NA <br /> 3/07 710 1 3,800 1,300 <0.033 <0.033 0.088 1.0 <0.033 <0.33 NA <br /> 5/08 250 8,600 1,200 <0.25 <0.25 <0.25 <0.25 <0.25 <0.01 NA <br /> 3/10 160 3,800 1,000 <0.1 1 <0.25 <0.25 <0.25 <0.25 NA NA <br /> TPHmo=TPH as motor oil B=benzene T=toluene E=ethylbenzene X=xylenes MTBE=methyl tert butyl ether TBA=tertiary butyl <br /> alcohol 1,2-DC-A=1,2-dichloroethane NA=not analyzed 1 =Ripon Farm Service diesel USTs(borings B14 to B16 on Site,see Figure 2) <br /> Maximum groundwater sample results are reported in micrograms per Liter u /L . <br /> Date TPHg TPHd TPHmo B T E X MTBE TBA 1,2-DCA <br /> 8/99 5 000 24,000 NA 690 31 48 570 3,500 <500 NA <br /> 1/00 3 900 2,600 NA 820 13 61 190 7,400 <1,650 NA <br /> 1/03 23),000 24,000,000 NA 250 <25 200 400 2,600 <500 <25 <br /> 2/04 7 300 260,000 NA 8.6 <0.5 10 7.8 1,400 <10 <0.5 <br /> 2/05 15),000 480 NA 8.5 1.8 0.56 10 310 95 <5 <br /> 5/051 1E,000 210,000' NA 2.6 1.1 8.4 4.6 960 620 <5 <br /> 3/06 :160 51,000 16,000 1.1 1.5 10 1.8 410 570 <2.5 <br /> 2/07 520 59,000 25,000 1 2.6 1.6 1.6 1.5 410 1,800 <10 <br /> 2/08 :140 110,000 37,000 1.8 1.6 <0.5 0.54 350 2,100 <10 <br /> 2/09 260 43,000 20,000 <1 <1 <1 <1 180 650 NA <br /> 4/10 530 86,000 45,000 <0.5 1.1 <0.5 <0.5 260 320 NA <br /> 7/102 ' 30 410 NA <0.5 <0.5 <0.5 1 <0.5 1 210 930 NA <br /> 2/11 78 170 1 NA 1 <0.5 <0.5 <0.5 <0.5 250 570 NA <br /> 8/11 ' 90 220 1 NA 1 <0.5 0.69 <0.5 <0.5 38 370 NA <br /> 1 =sampled af er piping release from above ground storage tanks 2=sampling changed from standard 3-casing volume purge to low flow <br /> camnhno. .ri#K cil;na-1^I^pn„r.nffp,emmnn•i�nn cfnrhi of Hn+h of n".ninn <br />