Laserfiche WebLink
Industry Standard Requirements for Tank Inspection Frequency <br /> For the sake of consistency,the standard for testing frequency for ConVault fuel and oil containment systems should be consistent <br /> with the requirements of STI SP001 which is detailed below and is normally a function of the size of the tank and its Category per <br /> SP007 Standard. <br /> Tank Categories <br /> The tank categories and inspection schedule from SP001 are to be utilized for ConVault tanks. <br /> Among other factors,owners should take a number of aspects into consideration such as the tank leak detection system,and <br /> that the monitoring equipment is in good working condition. <br /> Based on many considerations,the SPo01 standard classifies tanks into three categories.Depending on the risk a tank system <br /> poses to the environment if kept in service it is ranked as a category 1,2 or 3 tank.Category 1 tanks pose the least amount <br /> of risk and category 3 the highest. <br /> See Table 5.4 of the standard,reproduced here,for examples of tank configuration and AST category.Please note that if the <br /> AST bottom plate, other than its legs or supports, is in contact with the ground or a concrete slab, it is prone to corrosion <br /> and increased susceptibility to leakage. Shop Fabricated Tanks in contact with the ground or a concrete base are almost <br /> always vertical tanks. Such tanks are placed in Category 2 or 3.ASTs which are elevated,have a leak detection system, have <br /> spill control and have no part of the tank in contact with the ground(other than legs or supports)are classified as category <br /> 1 tanks. <br /> Table SA:Example Tank Configurations and AST Category <br /> Tank Configuration Tank has CRDM AST Category <br /> AST Incontactwithground No 2or3 <br /> ConVault P Pevated tank w/spill control&no part of AST in contact w/ground Yes 1 <br /> Vertical tan kw/RPB&spit ccontrol Yes 1 <br /> Vertical tank w/double bottom&spill control Yes 1 <br /> Double-wall AST Yes 1 <br /> AST w/secondary containment dike/berm � Yes 1 <br /> CRDM.-Continuous Release Detection Method—or Leak Detection System <br /> RPB:Release Prevention Barrier <br /> Inspection Type and Frequency <br /> The SP0001 standard requires different inspection types and different inspection intervals based on the tank size, tank <br /> category,and the risk it poses.The tank inspection intervals from SP001 are to be followed for ConVault tanks. <br /> In Table 5.5 of SP0001 (see next page),those portions pertaining to shop fabricated tanks up to 30,000 gallons have been <br /> highlighted showing inspection schedules for the different AST categories. <br />