SECURE PIPE <br />HANGER TO <br />STRUCTURE (TYP) <br />THREADED STEEL <br />ROD WITH NUT AND <br />WASHER BOTH <br />SIDES (TYP) <br />CLEVIS HANGER, <br />SHOWN FOR <br />CLARITY. SIZE <br />HANGER FOR COLD <br />PIPE OUTSIDE <br />DIAMETER PLUS <br />INSULATION <br />THICKNESS. DO NOT <br />PENETRATE <br />INSULATION WITH <br />HANGER <br />PROVIDE A SECTION <br />OF HIGH DENSITY <br />INSULATION OR <br />STYROFOAM BILLETS <br />AT EACH HANGEROF <br />COLD INSULATED <br />PIPE. <br />PROVIDE SHORT <br />INSULATION SHIELD <br />FOR LAPPING <br />INSULATION JACKET <br />OVER HIGH DENSITY <br />INSULATION OR <br />STYROFOAM BILLETS. <br />MAINTAIN VAPOR <br />BARRIER <br />M—MI9a <br />CLEVlS HANGER, <br />SHOWN FOR <br />CLARITY. SIZE <br />HANGER FOR HOT <br />PIPE OUTSIDE <br />DIAMETER <br />CUT INSULATION <br />TO FIT AROUND <br />HANGER. SEAL <br />EXPOSED <br />INSULATION ENDS <br />WITH JOINT <br />SEALANT <br />REFER TO SPECIFICATIONS FOR INSULATION TYPES, INSULATION THICKNESSES, <br />HANGER TYPES, HANGER ROD CONNECTIONS TO SRUCTURE AND HANGER SPACING. <br />INSULA <br />NO SCALE <br />IPE HANGER DE <br />STUB PIPE BELOW CEILING AT LOCATIONS SHOWN ON PLAN. <br />HANG PIPE AT HEIGHT AS REQUIRED TO ACHIEVE A 90 <br />DEGREE PENETRATION OF CEILING. <br />PIPE HANGERS TO <br />STRUCTURE ABOVE. <br />LENGTH AS REQUIRED <br />1] CEILING CEILING <br />PROVIDE ESCUTCHEONS <br />WHERE PIPE IS EXPOSED <br />USE FIVE INCH SCHEDULE 40 POLYVINYLCHLORIDE (PVC) PIPING, FITTINGS <br />AND COUPLINGS. USE MINIMUM QUANTITY OF COUPLINGS REQUIRED, <br />SOLVENT WELD JOINTS. USE LONG SWEEP ELBOWS AT BOTH ENDS, MINIMUM <br />TWENTY FOUR INCH RADIUS. AVOID ELBOWS IN HORIZONTAL RUN IF AT ALL <br />POSSIBLE. PROVIDE TEST OF CONDUIT AFTER ASSEMBLY TO VERIFY <br />WATER TIGHTNESS -- REPAIR ANY LEAKS DETECTED. MAINTAIN PRESSURE <br />UNTIL BEVERAGE LINES ARE INSTALLED. GENERAL CONTRACTOR WILL SEAL <br />ENDS OF CONDUIT WITH FOAM AFTER BEVERAGE LINES ARE INSTALLED IN <br />CONDUIT. <br />ABOVE CEI <br />NO SCALE <br />Cs7kIBig].rI <br />SET TANK AS PROVIDE LOCALLY - <br />CLOSE AS APPROVED SEISMIC <br />POSSIBLE TO WALL. STRAPS AROUND TANK <br />PROVIDE IN TOP AND BOTTOM <br />NON-COMBUSTIBLE THIRDS IN SUITABLE <br />BLOCKS FOR LOCATIONS (MINIMUM <br />SPACERS BETWEEN 4" FROM CONTROLS). <br />WALL AND TANK <br />ONLY IF REQUIRED ANCHOR STRAPS <br />FOR TANK ACCESS SECURELY TO WALL AS <br />OR CLEARANCE. REQUIRED BY STRAP <br />ANCHOR BLOCKS MANUFACTURER AND <br />TO WALL AS LOCAL CODES OR <br />REQUIRED. AUTHORITIES, BASED <br />ON TYPE OF WALL <br />FLOOR, EQUIPMENT CONSTRUCTION. <br />PAD, OR SUPPORT PROVIDE BACKBOARD <br />PLATFORM AS REQUIRED. <br />THIS DETAIL APPLIES TO WATER HEATERS, WATER SOFTENERS, <br />AND EXPANSION TANKS. ANCHOR TANK TO WALL AND/OR FLOOR <br />AS REQUIRED BY CODE FOR LOCAL SEISMIC CONDITIONS. <br />PROVIDE SEISMIC STRAPS (MEETING CODE REQUIREMENTS) AS <br />RECOMMENDED BY MANUFACTURER FOR SIZE AND TYPE OF TANK. <br />WATER HEATER AND EXPANSION TANK SHALL BE ANCHORED OR <br />STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE TO <br />EARTHQUAKE MOTION PER CALIFORNIA PLUMBING CODE SECTION <br />510.5, OR OTHER LOCAL CODE AS APPLICABLE. <br />TANK SEISMIC RESTRAINT <br />NO SCALE <br />INSTALL CONCENTRIC INTAKE <br />DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS. ADJUST TO SUIT FIELD CONDITIONS. <br />INSTALL THROUGH ROOF OR THROUGH WALL AS SHOWN ON PLANS. REFER TO <br />MANUFACTURER'S INSTALLATION MANUAL FOR MORE INFORMATION: MAINTAIN PROPER <br />DISTANCES FROM EACH OTHER, AND FROM OTHER CONSTRUCTION FEATURES; VERIFY PIPE <br />SIZE FOR MAXIMUM LENGTH OF RUN AND QUANTITY OF FITTINGS. DO NOT INSTALL BARE <br />PVC PIPE IN AIR PATH PLENUMS: WRAP PIPE WITH FIRE -BARRIER INSULATION IF ALLOWED <br />BY LOCAL AUTHORITIES, OR PROVIDE STAINLESS STEEL VENT PIPE, PER SPECIFICATIONS. <br />2SEALED COMBUSTION WATER HEATER VENT <br />NO SCALE <br />AUTOMATIC TRAP <br />CONNECT 1/2" PIPE (WITHOUT <br />AND EXHAUST VENT <br />INSTALL VENTS THROUGH <br />SHUT-OFF VALVE IN BRANCH) TO <br />TERMINAL FURNISHED BY <br />ROOF OR THROUGH <br />TRAP PRIMER VALVE OFF TOP <br />HEATER MANUFACTURER <br />EXTERIOR WALL AS <br />OF COLD WATER SUPPLY OR <br />ABOVE LOCAL MAXIMUM <br />CONVENIENT OR AS SHOWN <br />VALVED BRANCH PIPE. <br />SNOW DEPTH. <br />ON FLOOR PLAN. <br />INSULATE PIPE UPSTREAM OF <br />-- <br />i <br />TRAP PRIMER, BUT NOT <br />PROVIDE ROOF PENETRATION <br />PIPE HANGERS <br />DOWNSTREAM. <br />SEALING PER SEPARATE <br />REQUIRED BY <br />= <br />DETAIL. <br />I <br />INSTALL TRAP PRIMER LINE(S) <br />IF ALLOWED BY CONDITIONS <br />I <br />DOWNSTREAM OF TRAP PRIMER <br />AND LOCAL AUTHORITIES, <br />i <br />OR ABOVE EQUIPMENT.- _ <br />PROVIDE SCHEDULE 40 PVC <br />❑ <br />d <br />PIPE AND FITTINGS WITH <br />SOFT COPPER TUBING. INSTALL <br />PROVIDE DISTRIBUTION <br />SOLVENT WELD JOINTS, PER <br />SECURELY ATTACH TO <br />WITHOUT KINKS, AND SLOPE <br />SPECIFICATIONS, 3" OR 4" <br />SHELF WITH CEILING <br />Ii <br />SIZE AS SHOWN ON PLANS. <br />FLANGE, ALL -THREAD ROD, <br />REFER TO SPECIFICATIONS <br />AND SPLIT RING PIPEFOR <br />DRAIN. CONCEAL PIPE(S) IN <br />ALTERNATIVE <br />SUPORT. <br />INSTALLATION MATERIALS. <br />PROVIDE 3/4" FABRICATED <br />PRIMER VALVE. <br />CONDENSING WATER HEATER <br />PVC P -TRAP WITH MINIMUM <br />n <br />PER SPECIFICATIONS AND <br />1 " TRAP SEAL AND 4" <br />a <br />SEPARATE DETAIL. <br />LONG TAILPIECE FROM <br />PROVIDE FLOOR DRAIN <br />ELBOW FURNISHED WITH <br />EXPOSED IN UNFINISHED, <br />PROVIDE 6" HIGH <br />WATER HEATER. -/EQUIPMENT <br />PLATFORM. <br />THREADED TRAP PRIMER <br />ATTACH TO BACKBOARD <br />CONNECTION. PROVIDE <br />IF PIPE IS BELOW FLOOR SLAB <br />AND --OR SUSPEND FROM <br />r==' ON GRADE, PROVIDE 1/2" <br />ADAPTER. BRAZE JOINT <br />STRUCTURE ABOVE. <br />DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS. ADJUST TO SUIT FIELD CONDITIONS. <br />INSTALL THROUGH ROOF OR THROUGH WALL AS SHOWN ON PLANS. REFER TO <br />MANUFACTURER'S INSTALLATION MANUAL FOR MORE INFORMATION: MAINTAIN PROPER <br />DISTANCES FROM EACH OTHER, AND FROM OTHER CONSTRUCTION FEATURES; VERIFY PIPE <br />SIZE FOR MAXIMUM LENGTH OF RUN AND QUANTITY OF FITTINGS. DO NOT INSTALL BARE <br />PVC PIPE IN AIR PATH PLENUMS: WRAP PIPE WITH FIRE -BARRIER INSULATION IF ALLOWED <br />BY LOCAL AUTHORITIES, OR PROVIDE STAINLESS STEEL VENT PIPE, PER SPECIFICATIONS. <br />2SEALED COMBUSTION WATER HEATER VENT <br />NO SCALE <br />AUTOMATIC TRAP <br />CONNECT 1/2" PIPE (WITHOUT <br />PRIMER VALVE WITH <br />�T-� <br />SHUT-OFF VALVE IN BRANCH) TO <br />INTEGRAL AIR GAP. <br />i1i <br />TRAP PRIMER VALVE OFF TOP <br />INSTALL TRAP PRIMER <br />I <br />OF COLD WATER SUPPLY OR <br />MINIMUM 12" ABOVE <br />CEILING SPACE <br />VALVED BRANCH PIPE. <br />FLOOR FOR EVERY 20' <br />I <br />INSULATE PIPE UPSTREAM OF <br />OF DISCHARGE PIPE. <br />i <br />TRAP PRIMER, BUT NOT <br />AND SIZE OF BRANCH <br />AND AT LOCATION <br />DOWNSTREAM. <br />IF TRAP PRIMER IS <br />REQUIRED BY <br />= <br />INSTALLED IN PARTITION, <br />I <br />INSTALL TRAP PRIMER LINE(S) <br />PROVIDE ACCESS DOOR <br />I <br />DOWNSTREAM OF TRAP PRIMER <br />PER SPECIFICATIONS, <br />i <br />OR ABOVE EQUIPMENT.- _ <br />OR DISTRIBUTION UNIT USING 1/2" <br />❑ <br />d <br />11 <br />I <br />SOFT COPPER TUBING. INSTALL <br />PROVIDE DISTRIBUTION <br />i <br />i1i <br />WITHOUT KINKS, AND SLOPE <br />UNIT(S) WHERE MORE <br />I <br />I <br />Ii <br />CONTINUOUSLY TOWARDS FLOOR <br />THAN ONE TRAP IS <br />d" <br />e -H <br />DRAIN. CONCEAL PIPE(S) IN <br />SERVED BY ONE TRAP <br />PARTITION OR CHASE IN <br />PRIMER VALVE. <br />I <br />n <br />FINISHED AREAS. TRAP PRIMER <br />a <br />a <br />AND PIPES MAY BE INSTALLED <br />PROVIDE FLOOR DRAIN <br />d <br />EXPOSED IN UNFINISHED, <br />BODY OR P -TRAP WITH <br />�s <br />NON-PUBLIC AREAS. <br />THREADED TRAP PRIMER <br />d <br />CONNECTION. PROVIDE <br />IF PIPE IS BELOW FLOOR SLAB <br />SWEAT TO THREADED <br />r==' ON GRADE, PROVIDE 1/2" <br />ADAPTER. BRAZE JOINT <br />ELASTOMERIC INSULATION FROM <br />BELOW FLOOR SLAB ON <br />PRIMER CONNECTION TO 1" <br />GRADE. <br />ABOVE FLOOR SLAB. <br />PROVIDE TRAP PRIMERS WHERE SHOWN ON FLOOR PLANS, AND WHERE REQUIRED <br />BY LOCAL AUTHORITIES. PIPING ARRANGEMENT SHOWN IS SCHEMATIC: ADJUST <br />TO SWT FIELD CONDITIONS. REFER <br />TO SPECIFICATIONS AND PLUMBING FIXTURE <br />SCHEDULE FOR MORE INFORMATION. <br />INSTALL TRAP PRIMER VALVE AND <br />DISTRIBUTION UNIT PER MANUFACTURER'S RECOMMENDATIONS. <br />('r—'N� TRAP PRIMER <br />IN/OU_T_WALL <br />NO SCALE <br />3/4" PIPE FROM <br />COLD WATER SUPPLY <br />TO WATER HEATER, <br />WITH NO CHECK <br />VALVES INTERVENING <br />FDA -COMPLIANT <br />BUTYL DIAPHRAGM <br />WELDED STEEL <br />EXPANSION TANK WITH <br />POLYPROPYLENE LINING, <br />NSF APROVED FOR <br />DOMESTIC WATER <br />SERVICE <br />PIPE HANGER <br />NEXT TO ELBOW <br />X i-- PROVIDE <br />DIELECTRIC PIPE <br />UNION AT TANK <br />CONNECTION FOR <br />CONNECTION OF <br />DISSIMILAR METALS <br />AIR CHARGING <br />VALVE. FILL TANK <br />WITH AIR PRESSURE <br />TO MATCH WATER <br />PRESSURE. <br />PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO <br />SUIT FIELD CONDITIONS. FOLLOW MANUFACTURER'S <br />INSTRUCTIONS FOR INSTALLATION PROCEDURE. VERIFY <br />PROPER OPERATION WHEN INSTALLED, PROVIDE SEISMIC <br />STRAP OR BRACING WHEN REQUIRED BY LOCAL AUTHORITIES. <br />3 SMALL EXPANSION TANK <br />NO SCALE <br />INSTALL WITH MINIMUM 6" <br />CLEARANCE TO BUILDING <br />STRUCTURE ABOVE <br />PROVIIDE THERMOMETER IN <br />TEE FITTING <br />HOT WATER TO FIXTURES <br />PIPE UNIONS (TYPICAL) ABOVE TOP <br />OF TANK (TO FACILITATE REMOVAL <br />OF WATER HEATER) -a <br />PROVIDE DIELECTRIC PIPE UNION AT <br />TANK CONNECTION FOR CONNECTION <br />OF DISSIMILAR METALS (TYPICAL) <br />PROVIDE 12"WIDE x 12"DEEP HEAT <br />TRAP AT INLET AND OUTLET (TYPICAL)— <br />LINE SIZE GAS SUPPLY TO <br />WATER HEATER <br />GAS-FIRED WATER HEATER PER <br />SPECIFICATIONS AND SCHEDULE / <br />GAS COCK -' / <br />UNION WITH GROUND JOINT J <br />6" LONG DIRT LEG --`*'� <br />PROVIDE REDUCER AT EQUIPMENT <br />CONNECTION IF REQUIRED <br />PROVIDE PLATFORM. <br />ATTACH TO BACKBOARD <br />AND/OR SUSPEND FROM <br />STRUCTURE ABOVE, MINIMUM <br />6" CLEAR OF CEILING, IF ANY <br />SUSPEND PIPE FROM <br />ESCUTCHEON AT <br />STRUCTURE ABOVE, <br />CEILING PENETRATION <br />NOT FROM HOOD OR <br />CEILING <br />GAS COCK <br />DO NOT INSTALL <br />INSTALL AUTOMATIC <br />ANY GAS VALVES IN <br />GAS SHUT-OFF VALVE <br />CEILING SPACE <br />FURNISHED WITH <br />wCoLU <br />EXHAUST HOOD FIRE <br />EXHAUST HOOD <br />SUPPRESSION SYSTEM <br />PROVIDE QUANTITY <br />PIPE DROP OF SIZE <br />AND SIZE OF BRANCH <br />AND AT LOCATION <br />CONNECTIONS AS <br />SHOWN ON PLAN <br />REQUIRED BY <br />= <br />EQUIPMENT SERVED. <br />GAS PIPE HEADER ALONG <br />PROVIDE GAS COCK <br />WALL BEHIND COOKING <br />LOCATED WHERE <br />EQUIPMENT (OR INSIDE <br />ACCESSIBLE BESIDE <br />WALL IF INDICATED ON <br />OR ABOVE EQUIPMENT.- _ <br />PLAN), SIZES AS SHOWN <br />-• i ON PLANS <br />INSTALL FLEXIBLE <br />APPLIANCE �\-6" DIRT LEG AT BOTTOM <br />CONNECTOR HOSE OF RISER <br />FURNISHED WITH <br />KITCHEN EQUIPMENT CONNECT HOSE TO <br />KITCHEN EQUIPMENT <br />KITCHEN FLOOR---� - (TYPICAL) <br />REFER TO SPECIFICATIONS FOR MORE INFORMATION ABOUT PIPE, FITTINGS, <br />AND CONNECTIONS. PIPING ARRANGEMENT SHOWN IS SCHEMATIC; ADJUST <br />TO SUIT FIELD CONDITIONS. IF EXPOSED, ATTACH RISER AND HEADER TO <br />WALL WITH 1" CLEARANCE BEHIND PIPE (UNLESS INSTALLED INSIDE WALL <br />AS SHOWN ON PLANS). MAKE FINAL CONNECTION TO EQUIPMENT AS <br />RECOMMENDED BY MANUFACTURER. INSTALL ANY GAS PRESSURE <br />REGULATORS FURNISHED BY FOOD SERVICE EQUIPMENT CONTRACTOR. <br />7 COOKING APPLIANCE GAS PIPE <br />NO SCALE <br />N E <br />© <br />04 Lo m <br />co "T O <br />PROVIDE AUTOMATIC VACUUM e2 °E � <br />. <br />RELIEF VALVE ABOVE TOP >LL- W LL- <br />OF TANK ¢ ¢ -0 <br />nLL ----- -TYPICAL SHUT-OFF VALVE Z Lo a <br />f I Lu - -- - COLD WATER SUPPLY <br />TO WATER HEATER W p N CD <br />CHECK VALVE <br />COLD WATER BRANCH °O <br />TO EXPANSION TANK <br />Lo <br />-- INSTALL ASME TEMPERATURE AND cfl <br />PRESSURE RELIEF VALVE FURNISHED <br />WITH WATER HEATER SET TO OPEN AT <br />NOT MORE THAN 150 PSI. <br />CONNECT TO TOP OR SIDE OF <br />TANK AS REQUIRED FOR 0 <br />MODEL FURNISHED (TYPICAL) <br />PROVIDE HARD COPPER RELIEF VALVE C] <br />DISCHARGE PIPE FULL SIZE OF VALVE <br />OUTLET. DRAIN PIPE SHALL DRAIN INTO + z <br />MOP SINK. DRAIN PIPE SHALL TERMINATE w <br />A MAXIMUM OF 6 INCHES ABOVE THE MOP <br />7 SINK, U) <br />INSTALL DRAIN VALVE W❑ <br />FURNISHED WITH <br />WATER HEATER <br />REFER TO SPECIFICATIONS, SCHEDULES AND NOTES FOR MORE INFORMATION. PIPING ARRANGEMENT <br />SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. VERIFY CONNECTION SIZES AND <br />LOCATIONS PER MANUFACTURER'S REQUIREMENTS. REFER TO FLOOR PLANS FOR PIPE SIZES. <br />PROVIDE SEISMIC STRAP OR BRACING IF/AS REQUIRED BY LOCAL AUTHORITIES AND/OR SEPARATE <br />DETAIL. INSTALL WITH BOTTOM MINIMUM 6'-6" ABOVE FLOOR IF ABOVE JANITOR'S SINK; OTHERWISE <br />HIGH AS POSSIBLE. PLATFORM SHALL BE PLYWOOD ON UNISTRUT FRAME BRACKETED AND <br />ANCHORED TO WALL, AND/OR SUSPENDED FROM STRUCTURE ABOVE WITH THREADED ROD. POWER <br />WIRING AND DISCONNECT SWITCH ARE SPECIFIED BY ELECTRICAL. INTERLOCK OF AQUASTAT WITH <br />RECIRCULATION PUMP IS SPECIFIED BY ELECTRICAL IF REQUIRED. <br />4 GAS FIRED WATER HEATER OVERHEAD <br />NO SCALE <br />ROOF INSULATION <br />CORE DRILL ROOF OR <br />PROVIDE SLEEVE IF <br />REQUIRED BY TYPE <br />OF ROOF DECK. <br />PROVIDE FIRE STOP <br />SEAL BETWEEN PIPE <br />AND SLEEVE OR <br />DECK. <br />PROVIDE PIPE INCREASER ON <br />SMALLER VENT IF/WHERE <br />CODE REQUIRES A MINIMUM <br />3" VENT THRU ROOF <br />MINIMUM 12" ABOVE ROOF <br />NORMALLY. EXTEND TO <br />HEIGHT OF PARAPET WHEN <br />WITHIN 10' OF PARAPET, <br />OR ABOVE MAXIMUM LOCAL <br />SNOW DEPTH. <br />ANCHOR PIPE <br />TO STRUCTURE. <br />ROOF DECK <br />MINIMUM 12" <br />BELOW ROOF <br />REFER TO SPECIFICATIONS <br />FOR TYPE OF PIPE, <br />FITTINGS, AND CONNECTORS. <br />REFER TO PLANS FOR <br />SIZE(S) AND LOCATION(S). <br />LOCATE VTR MINIMUM THREE FEET FROM PROPERTY LINE, TEN FEET <br />HORIZONTAL OR THREE FEET VERTICAL ABOVE ANY BUILDING <br />OPENING OR FRESH AIR INTAKE, TWENTY FIVE FEET FROM ANY <br />OPENING OR FRESH AIR INTAKE IN MEDICAL FACILITIES AND ONE <br />FOOT FROM ANY VERTICAL SURFACE. REFER TO LOCAL CODES <br />FOR OTHER VENT TERMINATION REQUIREMENTS. LOCATE VTR <br />MINIMUM 18" FROM ADJACENT WALL, PARAPET, EXPANSION JOINT, <br />ROOF DRAIN, EQUIPMENT CURB, OR OTHER ROOF FEATURE. <br />OFFSET IN CEILING SPACE WHERE REQUIRED TO MEET THESE <br />CONDITIONS. INSULATE LAST SIX FEET OF VENT PIPE INSIDE <br />BUILDING PER SPECIFICATIONS. <br />VENT TH RU ROOF "VTR"} <br />NO SCALE <br />THIS DRAWING IS AN INSTRUMENT OF <br />SERVICE AND AS SUCH SHALL REMAIN <br />THE PROPERTY OF NEPTUNE DESIGN <br />GROUP LLC. UNAUTHORIZED USE OF <br />REPRODUCTION WITHOUT PERMOSION <br />OF THE ARCHITECT iS PROHIBITED. THIS <br />DRAWING IS ONLY FOR USE 1N <br />CONNECTION WITH THIS PROJECT AND <br />SHALL NOT SE USED FOR OTHER <br />LOCATIONS. COPYRIGHT 2018. <br />REVISION <br />IA I <br />A <br />DATE: 3.23.2018 1 <br />REVIEW SET <br />NOT FOR <br />PERMIT <br />PLUMBING <br />DETAILS <br />ci <br />w <br />w <br />0 <br />z <br />❑ <br />wCoLU <br />V <br />F- <br />2 <br />Z <br />H <br />w <br />V <br />acncQ© <br />= <br />V <br />0<ow-1 <br />= <br />Ln <br />Q <br />w <br />❑ <br />d <br />C) <br />o <br />d" <br />e -H <br />Q <br />v <br />n <br />a <br />a <br />d <br />�s <br />� <br />d <br />0 <br />REVISION <br />IA I <br />A <br />DATE: 3.23.2018 1 <br />REVIEW SET <br />NOT FOR <br />PERMIT <br />PLUMBING <br />DETAILS <br />