1 0 0 <br />SWRCB, January 2002 FINAL DRAFT Page 2 of 7 <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: ® Tank Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ® Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: 0 to 30" hg Dial Gauge Equipment Resolution: 2%@ Mid <br />Comments — (Include information on repairs made prior to testing, and recommended follow-up for failed tests.) <br />Sensors were reinstalled after containment testing was completed. <br />' Secondary containment systems where the continuous monitoring automatically monitors loth the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />Tank # 1 <br />87 Unleaded <br />Tank # 2 <br />89 /92 Unleaded <br />Tank # <br />Tank # <br />Is Tank Exempt From Testing?' <br />❑Yes ®No <br />❑Yes ®No <br />❑Yes ❑No <br />❑Yes ❑No <br />Tank Capacity: <br />12000 <br />6000/6000 Split <br />Tank Material: <br />Glasteel <br />Glasteel <br />Tank Manufacturer: <br />Modern <br />Modem <br />Product Stored: <br />87 Unleaded <br />89 /92 Unleaded <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />20 Minutes <br />20 Minutes <br />Test Start Time: <br />9:55am <br />11:25am <br />Initial Reading (RI): <br />10.00" hg <br />10.00" hg <br />Test End Time: <br />11:OOam <br />12:30pm <br />Final Reading (RF): <br />10.00" hg <br />10.00" hg <br />Test Duration: <br />65 Minutes <br />65 Minutes <br />Change in Reading (RF -RI): <br />0.00" hg <br />0.00" hg <br />Pass/Fail Threshold or Criteria: <br />0.00" hg <br />0.00" hg <br />Test Result <br />®Pass ❑Fail <br />®Pass ❑Fail <br />®Pass ❑Fail <br />❑Pass ❑Fail <br />Was sensor removed for testing? <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />❑Yes ❑No [:INA <br />❑Yes ❑No ❑NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />❑Yes ❑No ❑NA <br />❑Yes [:]No ❑NA <br />Comments — (Include information on repairs made prior to testing, and recommended follow-up for failed tests.) <br />Sensors were reinstalled after containment testing was completed. <br />' Secondary containment systems where the continuous monitoring automatically monitors loth the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />