Laserfiche WebLink
Page 2 of 8Our <br /> . <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer El Industry Standard ❑Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑Pressure El Vacuum ❑Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used:Vacuum Gage Equipment Resolution: 0-30 Hg <br /> Tank# 87 Tank# 91-Diesel Tank# Tank# <br /> Is Tank Exempt From Testing? ❑ Yes IKI No ❑ Yes rx-1 No ❑Yes❑ No ❑Yes❑ No <br /> Tank Capacity: 12000 12000 <br /> Tank Material: Steel Steel <br /> Tank Manufacturer: Glassteel II Glassteel II <br /> Product Stored: Reg Prem/Diesel <br /> Wait time between applying <br /> pressure/vacuum/water and starting 5 min 5 min <br /> test: <br /> Test Start Time: 09:30 09:30 <br /> Initial Reading(Ri): -10" -10" <br /> Test End Time: 10:30 10:30 <br /> Final Reading(RF): -10" -10" <br /> Test Duration: 1 hr 1 hr <br /> Change in Reading(RF-Ri): 0 0 <br /> Pass/Fail Threshold or Criteria: 0 0 <br /> TeSt.Resu[t: �,Pass E3 Fail 0 Pass Q Fail ❑Pass ❑-,Fail.. , ❑'Pass'❑ Fail <br /> Was sensor removed for testing? EI Yes ❑ No ❑ NA 21 Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> Was sensor properly replaced after O Yes ❑ No ❑ NA o Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> testing? <br /> Comments-(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary containment, <br /> such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment testing. <br /> {Califomia Code of Regulations,Title 23,Section 2637(a)(6)} <br />