Laserfiche WebLink
Page 3 of 8 <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: Piping Manufacturer 0 Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: 0 Pressure Vacuum Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Pressure Gauge Equipment Resolution: 0-30 psi <br /> Piping Run # 87 Piping Run # 91 Piping Run # Diesel Piping Run # <br /> "PipingMate6al:M FG FG FG <br /> Piping Manufacturer: UK UK UK <br /> Piping Diameter: 4" 4" 4" <br /> Length of Piping Run: 45' 40' 60' <br /> Product Stored: Reg. Prem. Diesel. <br /> Method and location of piping- <br /> run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 5 min 5 min 5 min <br /> starting test: <br /> Test Start Time: 09:40 09:40 09:40 <br /> Initial Reading(Ri): 5 psi 5 psi 5 psi <br /> Test End Time: 10:40 10:40 10:40 <br /> Final Reading(RF): 5 psi 5 psi 5 psi <br /> Test Duration: 1 hr 1 hr 1 hr <br /> Change in Reading(RF-Ri): 0 0 0 <br /> Pass/Fail Threshold or Criteria: 0 0 0 <br /> Test Result: ®Pass-0 Fait ;%; ®Pass D Fail, ®Pass. ® Fail ®Pass 0 Taal <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br />