Laserfiche WebLink
DISPENSER SHUTDOWN MAPPING VERIFICATION TEST <br /> Dispenser fueling point numbers FP: 7 FP: 8 <br /> ," 1�-...— Test Result(Y <br /> Dispenser was shutdown? Y <br /> Fuel was unable to be dispensed from fueling points associated with the dispenser? Y <br /> Dispenser was re-enabled? Y <br /> Fuel can be dispensed from fueling points associated with the dispenser? Y <br /> s <br /> .a tt.v.z-. �3P -... <br /> Vapor flow meter serial number 0826 786 <br /> Dispenser fueling point numbers FP:7 FP: 8 <br /> Low grade VAL result#1 1.11 1.03 <br /> ISD V/L value#1 1.25 1.18 <br /> Difference between V/L result#1 and ISD V/L value#1 (V/L—ISD V/L) .14 .15 <br /> Pass/Fail(Pass=difference within±0.15),if fail continue PASS PASS <br /> Low grade V/L result#2 <br /> Low grade V/L result#3 <br /> Average of 3 V/L results <br /> ISD V/L value#2 <br /> ISD V/L value#3 <br /> Average of 3 ISD V/L results <br /> Difference between Average V/L and Average ISD V/L values <br /> Pass/Fail(Pass=difference within±0.15) <br /> I declare, under penalty of perjury under the laws of the state of California that based on information and belief formed <br /> after reasonable inquiry, the statements and information provided in the document are true, accurate, and complete. <br /> Signature of Technician: Date: 7/11/2018 <br /> r, <br /> AUG 1 2618 <br /> YT <br /> HF-AJ H— <br /> Ver. 1.2—08.0 .08 <br />