Laserfiche WebLink
Emergency Vent Manufacturer-Primary Tank Morrison <br /> Emergency Vent Size-Primary Tank 6" <br /> Emergency Vent Model-Primary Tank 97y6/750cfr at 20psi <br /> Does the Emergency Vent Operate As <br /> Designed? es <br /> Is the Emergency Vent Properly Sized? Yes <br /> Emergency Vent Manufacturer-Secondary <br /> morrison <br /> Tank <br /> Emergency Vent Size-Secondary Tank 8" <br /> Emergency Vent Model-Secondary Tank 244-16oz/sq in <br /> Does the Emergency Vent Operate As <br /> Yes <br /> Designed? <br /> Is the Emergency Vent Properly Sized? Yes <br /> Other <br /> Tank Primary Level Gauge Type Clock gauge <br /> Tank Primary Level Gauge Manufacturer/ Morrison 818 <br /> Model No. <br /> Tank Primary Level Gauge Condition Good <br /> Tank Primary Level Gauge Accuracy Accurate <br /> Tank Secondary/Interstitial Level Gauge Type None <br /> Tank Secondary/Interstitial Level Gauge N/A <br /> Manufacturer and Model No. <br /> Tank Secondary/Interstitial Level Gauge N/A <br /> Condition <br /> Tank Secondary/Interstitial Level Gauge N/A <br /> Accuracy <br /> Other <br /> Overfill Protection As Required Per 40 CFR Observations Comments/Recommendations <br /> Overspill112.8/ <br /> Tank Overfill Protection Type Ext Alarm Sentry tank monitor <br /> Does the Tank Overfill Protection Operate As es <br /> Designed? <br /> Is the Overfill Alarm Set At 90%?Overfill N/A unknown <br /> prevention device set at 90%? <br /> Other <br /> Overspill Protection Observations <br /> Overspill Protection Type Oil Pan/Double Wall Tank pumps from large oil pan into tank. <br /> Overspill Protection Condition Good <br /> Other <br /> 5 <br />