Laserfiche WebLink
Grounding • Bonding • • Comments/Recommendations <br /> Are the Tanks Grounded And/Or Bonded No Ground tanks per NFPA 780 or other accepted industry <br /> Properly? standard. <br /> Other <br /> Stairways-Handrails-Platforms-Laddersi Observations Comments/Recommendations <br /> Stairways-Handrails-Platforms-Ladders No <br /> Other <br /> 5.0 External Shell <br /> I Coatings d��bservations Comments/Recommendations <br /> Tank External Coating Paint <br /> External Coating Condition Good <br /> Other <br /> Condition Of Welds IGood <br /> Corrosion No <br /> Evidence of Distortion No <br /> Mechanical Damage No <br /> Evidence of Leaks No <br /> Repads or Changes to Original Design? No <br /> Other <br /> Insulation Missing? N/A <br /> Evidence of Moisture? N/A <br /> Evidence of Mold? N/A <br /> Damage to Insulation? N/A <br /> Corrosion Under Insulation? N/A <br /> Other <br /> Standing Water(low areas)? No <br /> Coating Failure? INo <br /> Other <br /> 6.0 Next Scheduled Formal Inspection <br /> Comments <br /> The tank is equipped with spill control and/or CRDM (continuous release detection method) <br /> and is considered a Category 1 tank per table 5.5 of STI SP001.The next formal inspection <br /> Formal Inspection Is Required in (years): would be required required by the sites SPCC Plan.The inspection schedule is based on <br /> he site completing the recommended repairs as noted in the inspection report. If problems <br /> are identified during periodic inspections a formal inspection may required soon.The <br /> condition of the equipment may change after the issuance of this report. <br /> Other <br /> 7 <br />