Laserfiche WebLink
l l r77f4 X7'117-aRM"Er4 <br /> xizm WhL7irgs-Unpany <br /> Maximum Maximum <br /> Map Location and Possible Spill Probable Direction Secondary <br /> ID Potential Event Volume Discharge Rate2 of Flow Containment <br /> (gallons) <br /> XF-1 Transformers 240 6 gpm East to curb and gutter Active secondary containment <br /> Failure of Cooling Most likely<50 measures <br /> XF-2 System(puncture or 135 6 gpm East to curb and gutter Active secondary containment <br /> breach below product Most likely<50 measures <br /> XF-3 level) 135 6 gpm East to curb and gutter Active secondary containment <br /> Mishap during Most likely<50 measures <br /> maintenance <br /> 006 Diesel Gen-set, 1,026 Gradual to To storm drain system, Secondary containment within <br /> Outside west side of instantaneous, catch basins west double-walled steel tanks. <br /> warehouse- likely volume up <br /> Failure of AST(breach to 1,026 gal for Additional active secondary <br /> below product level) tank failure to containment measures. <br /> -Tank overfill secondary <br /> -Pipe failure <br /> -Leaking pipe or 159 gal/hr for pipe <br /> valve packing failure <br /> 007 Diesel Gen-set, 1,026 121 gal/hr for pipe To storm drain system, <br /> Outside east side failure catch basins east <br /> (south end) of <br /> warehouse Secondary containment within <br /> -Failure of AST double-walled steel tanks. <br /> (breach below product <br /> level) Additional active secondary <br /> -Tank overfill containment measures <br /> -Pipe failure <br /> -Leaking pipe or <br /> valve packing <br /> 13 MARTIN-BROWER <br />