C:CEjv;= n <br /> SWRCB,January 2002 Page of <br /> ii in.� n �r x(117 <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: X Tank Manutacturer Industry Standard: Prgfessional Engineer <br /> Other(Spec) nEPARINAENT <br /> Test Method Used: Pressure X Vacuum Ci Hydrostatic <br /> Other(Specify) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - %z"x-30"Hg. <br /> Tank# 1 Tank#2 Tank#3 Tank# <br /> Is Tank Exempt From Testing?' No No No <br /> Tank Capacity: 15K 15K 12K <br /> Tank Material: Fiberglass Fiberglass Fiberglas <br /> Tank Manufacturer: XERXES XERXES XERXES <br /> Product Stored: Regular 87 Regular 87 Super 91 <br /> Wait time between applying 10 Minutes 10 Minutes 10 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 12:55 12:45 12:35 <br /> Initial Reading(Ri): -10"Hg. -10"Hg. -10"Hg. <br /> Test End Time: 1:55 1:45 1:35 <br /> Final Reading(RF): -10"Hg. -10"Hg. -10"Hg. <br /> Test Duration: 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-Rj): 0"Hg. 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2"Hg. ➢ -2"Hg. ➢ -2" Hg., <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? No No No <br /> Was sensor properly replaced and N/A N/A N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />