SWRCB,January 2002 Page .^of <br /> 7. UNDER-DISPENSER CONT.A.XXMENT(tMQ TESTEM1G <br /> Test ethod Developed sy: 0 LDC Manufacturer _ Industry Standard X.Professional Engineer <br /> M <br /> L7 Other(Spec&) _ <br /> I est.Method Used: n Pressure C Vacuum X Hydrostatic <br /> C Other(Specify) _. <br /> Test Equipment Used: Caldwell Level Change Indicator Equipment Resolution: .002 <br /> UDC#1&2 UDC#3&4 UDC#5&6 UDC#7&8 <br /> UDC Manufacturer: Bravo 11 Bravo Bravo _ Bravo <br /> UDC Material: Fiberglass Fiberglass' ' Fiberglass Fiberglass <br /> UDC Depth: J 29" 29" 29" 29" <br /> Height from UDC Bottom to Top 10" 10" <br /> of Hi hest PipjEg Penetration: — <br /> Height from UAC Bottom to No Electrical _ No Electrical No Electrical No Electrical <br /> Lowest Electrical Penetration: Penetrations Penetrations Penetrations Penetrations <br /> Condition of UDC prior to Dry Dry Dry Lary <br /> rj'urb!j�ne <br /> of UDC Tested Water Level 12" Water Level 12" Water bevel 12" Water Level 12" <br /> zbinc shut down when <br /> nsor detects liquid(both Yes 'Yes Yes Yes <br /> and washutdown response time Not Alarmed Not Alarmed Not Alarmed Not Alarmed <br /> Is system programmed for fail- Yea Yes Yes Yes <br /> safe shutdown?* <br /> Was fail-safe verified to be No No No No <br /> operational', <br /> Wait time between applying 5 Minutes 5 Minutes S Minutes 5 Minutes <br /> water and starting test <br /> Test Start Time. 12:35 12:40 12:45 1.7;50 <br /> Initial Reading(Rz): .001 .001 001 .001 <br /> Test End Time: 1:05 1:10 1:15 1:20 <br /> Final Reading(RF): .001 -001 .001 •001 <br /> Test Duration: 30 Minutes 30 Minutes 30 Minutes 30 Minutes <br /> Change in Readbi (R❑-Rj): 0 0 0 0 <br /> Pass/Fail Threshold or Criteria: .005/30 Minutes 005/30 Minutes .005/30lvlinutes 005/30 Minutes <br /> Test-Res>Ylt: <br /> 7Pags7 Pass „? <br /> Was sensor removed for testin . Yes Yes Yes Yes <br /> Was sensor properly replaced and Yes Ye$ Yes Yes <br /> verified functional after testin ? - <br /> Comments—(include information on repairs made prior to testing, and recommended follow-z[p for ailed tests) <br /> V LU 1i <br /> ' If the entire depth of the UDC is not tested,specify hoNv much was tested. If the answer to gDy of the questions indicatod with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />