SAN J O A Q U I N Environmental Health Department <br /> COUNTY <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> Yosemite Avenue Arco AmPm 1 1711 E Yosemite Ave, Manteca June 05,2018 <br /> UST System Observations <br /> 319 CCR 2635(b) No spill bucket,failed to contain five gallons,or failed to provide a means to keep it empty ❑V ❑R ❑COS <br /> 320 CCR 2635(b)(2) Overfill prevention system not present or failed to meet overfill requirements ❑V ❑R ❑COS <br /> 321 CCR 2635(b)(2) Overfill prevention was overridden ❑V ❑R ❑COS <br /> 322 HSC 25281.6(a) Unburied below grade emergency generator system failed to meet exemption status ❑V ❑R ❑COS <br /> 323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status ❑V ❑R ❑COS <br /> 324 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 325 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R a COS <br /> 326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 327 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 328 HSC 25298 Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 329 HSC 25298 Failed to comply with all permanent closure requirements ❑V ❑R ❑COS <br /> 330 CCR 2636(0(6) Failure to meet all requirements in lieu of a line leak detector for emergency generator tank system o V o R ❑COS <br /> 331 CCR 2630(d) Secondarily contained piping not maintained to allow liquid to drain into sump ❑V ❑R ❑COS <br /> 332 CCR 2631(b),2631(d) Primary and/or secondary containment not constructed in accordance with the established standards ❑V iiR ❑COS <br /> Single-Walled Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V a R o COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V n R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted General violation ❑V ❑R n COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 105 CCR 2632(d)(1), 2634(d) Failed to have an approved UST monitoring plan. <br /> The monitoring plan is not current and/or not approved by the EHD. The monitoring plan found on site stated that <br /> the 87 product tank had a 99LD-2000 line leak detector however on CERS and while on field Veeder Root PLLD <br /> was noted, also a 208 sensor was observed on the 87-1 fill sump, however in the monitoring plan only sensor 323 is <br /> listed. The monitoring plan must be uploaded to the California Environmental Reporting System (CERS).The <br /> owner of the site made the appropriate corrections to the monitoring plan that was on site while inspector was on <br /> site to correct the violation. <br /> This was corrected on site. <br /> This is a repeat violation, Class II. <br /> FA0003612 PR0231455 SCO01 06/05/2018 <br /> EHD 23-01 Rev.10/31/2017 Page 3 of 5 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjcehd.com <br />