Laserfiche WebLink
2.5 COMPONENTS <br /> A. FUSES <br /> 1. Fuses used in circuits 200 VAC and above shall be time- delay type FNQ or approved <br /> L equal, 13/32"x 1-1/2", and have an interrupting rating of 10,000 AIC at 500 VAC. Fuse <br /> holders shall be of the barrier type and rated 600 VAC. <br /> 2. Fuses used in 120 VAC shall be time-delay type MDL or approved equal, 1/4" x 1-1/4", <br /> and have an rating of 250 VAC. Fuse-holders shall be of the terminal block type. <br /> 3. Fuses used in signal and 24 VDC circuits shall be fast acting type ABC or approved <br /> equal, 1/4" x 1-1/4", and have an rating of 250 VAC. Fuse-holders shall be of the <br /> terminal block type. <br /> 4. Fuses shall be sized in conformance with the NEC. <br /> ' B. SWITCHES AND PUSHBUTTONS <br /> 1. Switches(SS) and pushbuttons(PB)for general purpose applications shall be water and <br /> oil tight as defined by NEMA 13, corrosion resistant as defined by NEMA ICS 6-110.58, <br /> U.L. listed, standard 30 mm diameter, with round plastic clamp ring. Switches shall be <br /> Westinghouse P132, IDEC, or equal. <br /> 2. Switches and pushbuttons shall have contacts rated 10 amperes continuous and 600 <br /> VAC. <br /> 3. Manufacturer's standard legend plates shall be provided. <br /> 4. Selector switch handles and pushbutton caps shall be black. <br /> 5. Selector switches for hand-off-auto (HOA) applications shall have the hand position to <br /> the left, off in center, and auto in the right position. <br /> ' ELECTRICAL <br /> 16000 - 17 <br />