Laserfiche WebLink
C. RECEPTACLES <br /> 1. General purpose receptacles shall be duplex and rated 20 amps, 120 VAC, 2 pole, 3 wire <br /> grounding, NEMA 5-20R configuration, specification grade, and side wired to screw <br /> terminals. Face color shall be brown in industrial areas and white or ivory in finished <br /> areas. General purpose receptacles shall be Bryant, Hubbell, or approved equal. <br /> 2. GFI(ground fault circuit interrupting) receptacles shall be used for providing power to <br /> miscellaneous cord powered equipment. GFI receptacles shall be duplex, 20A, 120V, <br /> with "test" and "reset" buttons with shallow design for mounting and standard screw <br /> terminals for direct wiring. Receptacles shall be designed, manufactured, and tested to <br /> prevent nuisance tripping from voltage spikes, RFI, EMI, or electronic component <br /> failures. Chaining multiple receptacles from one GFI unit is not acceptable. GFI <br /> receptacles shall be Arrow-Hart "specification grade" or approved equal. <br /> D. DEVICE PLATES and COVERS <br /> r1. General purpose device plates and covers shall be anodized aluminum. Plates or covers <br /> shall be attached with stainless steel screws. <br /> 2. Weatherproof switch, outlet, and receptacle boxes shall be fitted with gasketed covers <br /> rated for wet locations in accordance with NEC 410-57. Each access cover shall have <br /> a gasketed spring door to maintain the weatherproof integrity. Screws and hinge springs <br /> shall be stainless steel. Weatherproof access covers shall be Appleton "FSK" or approved <br /> equal. <br /> 2.9 TERNIINAL AND PULL BOXES <br /> A. PULL BOXES, UNDERGROUND <br /> Pull boxes, where shown or required by length of conduit runs, shall be prefabricated <br /> reinforced concrete type with steel covers. The pull box size shall be the size shown on the <br /> Drawings or larger to allow for adequate pull area. Extension sections shall be provided as <br /> necessary to reach the depth of underground conduits. Boxes located in paved areas or other <br /> areas in which vehicles may travel shall be IV20 loading rated and have traffic covers. Steel <br /> covers or lids shall be galvanized. Pull box covers shall be labeled power, signal, ground, <br /> utility,telephone,whichever applies. Pull boxes shall be Christy Concrete Products, Brooks, <br /> or approved equal. <br /> ELECTRICAL <br /> 16000 - 25 <br /> i <br /> 1 <br />