Laserfiche WebLink
All Single • Double <br /> A9. PIPING AND SUMP CLEARANCES A10. PILLIN a TANKS <br /> Tanks with Bottom Sumps <br /> When installing a tank equipped with a bottom sump, ex- <br /> cavating and bedding must be modified to provide: Do not fill tank with product or water for hold-down until <br /> backfilling Is even with top of tank or tank damage can <br /> ♦ A hole centered at the sump location. occur. <br /> ♦ Hole should be 12" deep x 24" diameter. Exception - "Installation Procedure-Wet Hole" section. <br /> After the tank is placed,the void surrounding the sump must be: <br /> ♦ Hand backfilled and All. VENTING <br /> ♦ Hand tamped prior to adding backfill around tank or ♦ All tanks must be vented. <br /> use a long handled curved probe to fill hole. ♦ Tanks are designed for operation at atmospheric pres- <br /> External Piping sure only (except for use with vapor recovery systems <br /> ♦ The pump and attached piping must be free to move provided the pressure or vacuum does not exceed 1 psi.) <br /> with the tank (see figure 23). ♦ The vent opening should be the same diameter or larger <br /> ♦ Use a fill box or street box to isolate the piping from the than the piping used to remove product. <br /> traffic pad. ♦ For double-wall tanks, if the annular space is vented, it <br /> ♦ Take precaution during construction to make sure no must be vented independently from the primary tank. <br /> damage occurs to the exposed piping and fittings. ♦ For hydrostatically monitored double-wall tanks,the an- <br /> FIGURE 23 nular space must be vented at all times. <br /> External Piping <br /> IsolatePiping .. PRESSURIZED PRODUCT DELIVERIES <br /> from Traffic <br /> CAUTION <br /> :Slabs: <br /> Pressurized product deliveries are not recommended <br /> AS TANK DAMAGE MAY OCCUR. <br /> ♦ If the delivery vehicle uses pumps to fill the tank: <br /> ❑ Install overfill,shut-off equipment in the lines and on <br /> the truck to prevent the tank from being overfilled. <br /> Internal Piping ❑ Overfilling the tank under pressure will damage <br /> ♦ Internal piping must terminate a minimum of: the tank,even if the tank vent is unrestricted. <br /> ❑ 4"from the tank bottom(4',6',8', 10'diameter tanks). ❑ Do not use a ball float valve for overfill protection. <br /> ❑ 6" from tank bottom (12' diameter tanks). <br /> (see figure 24) Al2. MANWAY AND MANWAY EXTENSIONS <br /> ♦ A fill tube insert must be installed at the tank gauging <br /> fitting if the manual dipstick method is used to inven- <br /> tory tanks to ensure the dipstick point of impact is <br /> aligned with the tank bottom protector plate. <br /> Do Not enter tank unless following OSHA guideilnea <br /> FIGURE 24 for confined space entry. <br /> Internal Piping Entry Can Result in: <br /> 4'-10' 12' <br /> dia. dia. <br /> Tanks Tanks <br /> Oct <br /> 4"min 6"min <br /> / ASPHYXIATION FIRE EXPLOSION <br /> CONTINUED ON PAGE 16 <br /> 15 <br />